Kalvis Kalvis-100MG Скачать руководство пользователя страница 12

12 - 

5.1.  Smoke discharge system 

Requirements: 

  In order to ensure normal operation of the boiler, continuously permanent sufficient chimney draught has to 

be  ensured  (

see  Table  1

). 

Smoke  extraction  fan  (smoke  exhauster)  has  to  be  installed  in  the  smoke 

discharge  circuit

.  In  the  case  of  restructuring  or  building  new  boiler  house,  in  order  to  reduce  harmful 

environmental impact, it is recommended to install a multicyclone (

see fig. 5, A and C

).  

  Height  of  the  chimney  shall  be  selected  by  designer  in  accordance  to  environmental  requirements  of  the 

location. 

  Smoke  and  air  ducts  of  the  boiler  houses  have  to  be  made  of  steel  (round  or  rectangular)  with  thermal 

insulation.  

  Flue  pipe  shall  be  installed  with  the  inclination  of  no  less  than  10  per  cent  and  the  bends  towards  the 

chimney of no more than 45

  Flue pipe can be installed not only directly from the end, but also by turning the branch pipe to one or  the 

other side of the collector, counterchanging with sooth removal lids. 

  Smoke  exhausters  have  to  be  installed  for  each 

boiler  separately,  according  to  manufacturer’s 

recommendations, taking into account the multicyclone, if installed. Frequency converters are recommended 
to use for smoke exhauster efficiency control in order to ensure economic and reliable operation of the boiler. 
One  shared  or  several  separate  chimneys  for  each  boiler  can  be  installed  in  the  boiler  houses.  If  shared 
chimney  is  installed,  each  boiler,  on  separate  branches,  shall  have  smoke  exhauster 

(see  fig.  5,  C

).

  It  is 

prohibited to install one smoke exhauster for two or more boilers (see fig. 5, D

). 

  Multicyclone  is  used  to  separate  ash  and  other  solid  volatiles  from  the  exhaust  gas  smoke).  Its  type  and 

efficiency is selected according to volume of combustion products, boiler power, following the manufact

urer’s 

recommendations. Multicyclones are installed behind the boiler and before the smoke exhauster (

see fig. 4, 

A

). 

It is prohibited to install multicyclone behind the smoke  exhauster 

(

see fig. 5, B

). When there  are 

several boilers, multicyclones are installed separately for each boiler (

see fig. 5, C

). Multicyclone installation 

has to be carried out in accordance with the building standards valid in the country of boiler operation. 

  Fixed  points  of  measurement  of  discharged  smoke  draught,  temperature  and  eco  parameters  have  to  be 

installed in the flue pipes.  

  Explosion isolation valves have to be installed in the smoke ducts where explosive gases can accumulate. 

  Holes for sooth removal with sealing doors have to be installed in the smoke ducts and chimney. 

  Drainage system for condensate collection and discharge has to be installed at the bottom of chimney. 

 

 

Fig. 5.  

Model systems for smoke discharge to chimney: 

1. Boiler.  2. Multicyclone.  3. Smoke exhauster. 4. Chimney.  B and D are improper options. 

 

As the boiler has high rates of efficiency, aerodynamic resistance gets larger and smoke temperature gets 

lower,  the  chimney  draught  has  to  be  higher  than  for  the  boilers  with  lower  technical  rate.  Flue  pipe  and 
chimney have to meet the following requirements (

see fig. 5

): 

Содержание Kalvis-100MG

Страница 1: ...SOLID FUEL WATER HEATING BOILER WITH PELLET BURNER KALVIS 100 MG 500 MG INSTALLATION AND SERVICE MANUAL LST EN 303 5 2012 20548 87 20548 93 Made in Lithuania Made in Lithuania...

Страница 2: ......

Страница 3: ...use it contact the seller Legend Important information or useful suggestions on installation or operation of the product Warnings about concerns for your health or property safety and correct operati...

Страница 4: ...ical part of the boiler 13 5 4 Boiler commissioning 14 6 Boiler operation 14 6 1 Preparation for work 14 6 2 Fuel container filling 14 6 3 Stoking 15 6 4 Maintenance 15 6 5 Boiler equipment servicing...

Страница 5: ...em with water The water in the heating system and boiler should not freeze up When boiler is in operation to close supply and return line valves To change the design of the boiler It is necessary to c...

Страница 6: ...dangerous for further boiler operation or operating personnel vibration knocks inside the boiler noise exhaust gas explosions in the pipeline damaged fittings pipes etc In the case of sooth and fuel p...

Страница 7: ...n note has to be made in this document under Installation Report Installed and connected boiler has to be checked by fire fighters It is strongly prohibited to fire the boiler without having filled it...

Страница 8: ...ed according to the requirements of STR 2 01 02 2016 Projecting and Certification of Energy Performance of Buildings expressed for Energy Performance of Buildings Classes B and C 3 Using 8 wood pellet...

Страница 9: ...burner L1 mm mm 1140 5 2990 5 1260 3110 1420 3350 1420 3650 Mass no more than 10 kg 2500 5 2580 3000 3420 1 Wood pellet quality shall be in line with DIN 51731 DIN plus standards 2 Energy quantity ca...

Страница 10: ...orative panels 21 Ash container 22 Actuator for ash from boiler extraction auger 23 Protective screw connecting the ash removal auger with its actuator 24 Tray for ash from the boiler 25 Water outlet...

Страница 11: ...stallation in the hearth door Distances from partitions are given in the boiler house project For maintenance of turbulizers and ash removal auger extraction leave a sufficient distance in front of th...

Страница 12: ...iler on separate branches shall have smoke exhauster see fig 5 C It is prohibited to install one smoke exhauster for two or more boilers see fig 5 D Multicyclone is used to separate ash and other soli...

Страница 13: ...east 5 minutes If as a result there are no leaks or weeping at maintained pressure this means that the boiler is fit for operation After completion of the test reduce pressure in the system down to th...

Страница 14: ...peration In order to ensure proper operation of the equipment make sure to study all given boiler burner and control unit manuals 6 1 Preparation for work When firing the boiler it is necessary to che...

Страница 15: ...ation about burner operation and control When boiler is operating in a stabile mode make sure that there are no water leakages knocks hydraulic shocks or penetration of discharged combustion products...

Страница 16: ...ed via dismountable joints Dismountable joints are mounted as follows open the door of heat exchanger at a minimum just to insert hand take off each turbulizer and insert part of its dismountable join...

Страница 17: ...3 Smoke temperature is too high Heat exchanger is sooty Clear sooth away from hearth surfaces Sediment accumulation inside the heat exchanger Adjust heat exchanger cleaning device Too high chimney dr...

Страница 18: ...opes during operation can wear out burn out They are available in the shop or at manufacturer Also see fig ECO BURNER UNI MAX 100 1000 kW Pellet Burner Operation Manual The heat exchanger door rotatio...

Страница 19: ...manufacturer s fault Burner guarantee service rules are described in ECO BURNER UNI MAX 100 1000 kW Pellet Burner User Manual In the case of boiler malfunction call by phone and when the firm s repres...

Страница 20: ...e of malfunction we recommend the following contacts Company Address Telephone Manufacturer Kalvis UAB Pramon s 15 LT 78137 iauliai Lithuania Telephone 370 671 88891 E mail prekyba kalvis lt Guarantee...

Отзывы: