21
REQUIRED MAINTENANCE CONTINUED...
Semi-annual maintenance of the Kitchen Mister System
Is required by NFPA-17A and Buckeye Fire Equipment
And must be performed by a factory trained, Authorized
Buckeye Fire Equipment Dealer. Semi-annual
Maintenance shall include the following:
Check that the hazard area has not changed.
1
Check the cylinder pressure gauge, making sure it is in the operable range.
2
Check all nozzle orifices to assure that they are unobstructed and that all nozzle caps are in
3
place.
If any BFR-UBC stainless steel metal caps are used, they must be removed, cleaned and
4
checked to assure that they slide easily on and off the nozzle body. If the cap does not slide
easily off the nozzle tip, the o-ring and cap must be replaced.
Remove the face plate from the control head.
5
Remove the actuation nitrogen cartridge from the systems releasing module. If the use of the
6
Keeper pin is desired to prevent the operation of the gas valve and miniature electric
Check entire system for mechanical damage.
7
Inspect fusible link detection line for grease build-up or mechanical damage. Replace corner
8
pulleys, or conduit if necessary.
Activate the Systems Releasing Module by releasing tension from the end of the fusible link line
9
by cutting or melting the last link. Make certain that the Systems Releasing Module fires, the
gas valve closes, and all auxiliary devices connected to the micro-switch operate or stop.
Replace all fusible link detectors.
10
Reset the Systems Releasing Module and then activate the system by using the remote pull
11
station. Make certain that the Systems Releasing Module fires, the gas valve closes, and all
auxiliary devices connected to the micro-switch operate or stop
After the SRM has been tested and is functioning properly, the system can be put back into
12
service.
If a Keeper Pin was used, remove it from the Systems Releasing Module.
13
Before installing the Nitrogen Cartridge it is necessary to make sure that the Actuating Pin is
14
moving freely. Insert the Actuation Pin Resetting Tool into the threaded hole of the Manifold
Mounting Block where the Nitrogen Cartridge is installed and then remove the BFR-PRT.
Install the Nitrogen Actuation Cartridge by completely screwing the cartridge into the manifold
15
block.
Re-install the Systems Releasing Module cover.
16
Verify that the date on the cartridge is visible in the viewing window
17
Annual
:
1.
Replace Fire Damper
Annual maintenance of the Kitchen Mister System
Is required by NFPA-17A and Buckeye Fire Equipment
And must be performed by a factory trained, Authorized
Buckeye Fire Equipment Dealer. Annual
Maintenance shall include the following:
Continued on next page...