4. Mounting and installation
15
Ferriferous materials can block the remote control signal. Take this
into account during installation. The signal strength is also weaker
if there is an intermediate wall. Check by pressing keys and on
the remote control simultaneously. If both figures exceed -80 (e.g.
-60), then Kal-fire guarantees good functioning.
The technical box must not become warmer than 60 C, otherwise
the Fairo will go into safety mode.
Conversion to a different category of gas is only permitted by the
producer or the installer in cooperation with the producer.
3.
Before connecting the gas, check the entire installation for leaks.
4.
Check the pre-pressure using a gas pressure meter and ensure that
all soiling is removed from the pipes; this is to prevent blockages and
obstructions. The pre-pressure must correspond with the pressure
stated on the CE-identification plate. If the pipes used are too small,
the pre-pressure may drop during use. The difference may not be
more than 2mbar.
4.5
Connecting the radiographic remote control
The Fairo has a radiographic remote control. Place a 230V earthed
socket, a phase and a zero.
The Fairo is phase sensitive. Please take this into account. If you
start the Fairo and an F08 malfunction occurs, turn the plug. This is
not possible in every country. In the female plug it is possible to
reverse the polarity of the phase wire and the zero wire.