5.6. Alarms.
1. Air filter alarm.
a. Air filter blocked. The panel displays AIR BLOCK when pressure differential switch closes.
b. Air filter running time alarm. Displays “AIR TIME END” when the running time of the air filter
terminates.
2. Oil filter alarm.
a. Oil filter blocked. The panel displays OIL BLOCK when pressure differential switch closes.
b. Oil filter running time alarm. Displays “OIL TIME END” when the running time of the oil filter
terminates.
3. O/A separator alarm.
a. O/A separator blocked. The panel displays O/A BLOCK when pressure differential switch closes.
b. O/A running time alarm. Displays “O/A TIME END” when the running time of the oil separator
terminates.
4. Lubricant oil alarm.
Displays “LUBE TIME END” when the running time of the lubricant oil terminates.
5. Grease alarm.
Displays “GREASE TIME END” when the running time of the grease terminates.
6. High discharge temperature alarm.
Displays “DISC T HIGH” when the discharge temperature is higher than the ALARM DISC T set in
the FACTORY PARAMETERS menu.
5.7. Controller protection
1. Motor protection