KRSD series
present or the fan is not required to be
protected.
FAN STOP T.
*** ˚C
Fan will stop if discharge temperature is
bellow this setting.
ON/OFF DELAY
TIME PRE-SET
MOTOR START
0008S
When using the controller to protect the
motor, is set to bypass the motor
overload protection on start up. It is
required that the time set here will not
meet the impulse starting current of the
motor, the value here must be longer
than the STAR DELAY TIME plus LOAD
DELAY TIME
FAN START
0006S
When using the controller to protect the
fan motor, it is set to bypass the fan
motor overload protection on start up. It
is required that the time set here will not
meet the impulse starting current of the
motor.
STAR DELAY
0006S
Star-delta changeover time.
LOAD DELAY
0002S
Delay to load when running in delta.
EMPTY DELAY
0020M
When running continuously unloaded,
the machine will automatically stop after
this time.
STOP DELAY
0010S
Run on time after the “Stop” button has
been pressed.
START DELAY
0100S
Machine cannot be restarted before this
set time after stopped or over time
operation unloaded.
STANDBY DELAY
TIME
0000S
Additional functions.
DRAIN OPEN TIME
0002S
Continuous draining time during the
automatic draining control.