OPzV Battery Operation Manual

11

Mon

thly Maintenance

Items

Details

Benchmarks

Maintenance

Total b

attery gro

up voltage

Use multi-meter

check total voltage

across positive and

negative terminal

1.The value of measured

and displayed on

equipment should be

close.

2. Voltage error after

compensation should be

less than ±50mV

Adjust the charging voltage to recom

mended range if there is a deviation;

Repair the equipment if voltage can’

t be adjusted.

Battery

appearan

ce

Bulge, leakage

or damage

Appearance should be

OK

Replace the battery if bulge, leakage

or damage

Dust, dirty

Clean

Cleaning

Connectors,

terminals

No rust

Clean and anti rust dealing

Battery

surface te

mperature

Use infrared

thermometer

measure surface

temperature

Less than

Further check and analysis if high

temperature found

Quarterly Maintenance

Yearly Maintenance

Items

Details

Benchmarks

Maintenance

Items

Details

Benchmarks

Maintenance

Float

voltage
for each
battery

Measure the voltage of
each battery under floatin
g, using a meter with four

and half digits.

Voltage difference
less than
2V: 90mV
6V: 240mV
12V:480mV

If there is a deviation, discharge the
batteries and perform a equalizing ch
arging, observe for one through two
months under floating. Contact us if
no improvement.

Correct
the

low

voltage
batteries

If more than two cells’
voltages are less than
2.16V/cell after
temperature adjustment,
the batteries need
equalization charging.

Float voltage

2.16V/cell

If battery float voltage less than
2.16V/cell after equalization charge,
the battery need do a 80% capacity
test.

Activated
discharge

Perform a discharge-char
ge cycle, using lower
level of equalizing charge
voltage for the charge.

Discharge around
30% of the
nominal capacity.

Perform the discharge-charge cycle if

no power-off for six months.

Содержание OPZV Series

Страница 1: ...OPZV SERIES TUBULAR GEL BATTERY OPERATION MANUAL Version 1 1...

Страница 2: ...2 3 Working Principle 3 PART TWO OPERATION AND MAINTENANCE 4 1 Operation Condition 4 2 Capacity 4 3 Temperature 5 4 Charge and discharge requirements 7 5 Storage 10 6 Maintenance 10 PART THREE BATTER...

Страница 3: ...ction The batteries for replacement should be used as the same as the old ones in model and type Warning Do not smoke or use fire near batteries Warning Do not use any organic cleanser to clean batter...

Страница 4: ...l formula active material Valve Made of acid proof aging proof synthetic rubber Flame arrestor With acid proof explosive proof functions 2 Product Specifications Model Nominal Voltage V Capacity Ah 10...

Страница 5: ...eparator to set up oxygen cycle principle Battery is full of gel electrolyte inside and A 3 D porous network is formed with framework of SiO2 The net contains electrolyte necessary for battery At init...

Страница 6: ...y The capacity can be expressed in Rated Capacity or Actual Capacity The Rated Capacity please sees Table 1 1 The Actual Capacity is the product of the discharge current and the discharge time the uni...

Страница 7: ...0 2C 1 80 0 2C I 0 6C 1 75 0 6C I 1 0C 1 70 1C I 2C 1 60 3 Temperature 3 1 Available Capacity vs Ambient Temperature Temperature affects capacity of the battery Fig 3 1 is the available capacity curve...

Страница 8: ...y at 25 And temperature compensation coefficient is 3Mv cell Table 3 3 Floating Voltage of VRLA Battery 25 Series Floating voltage V cell OPzV 2 23 0 02 The formula to calculate float voltage at diffe...

Страница 9: ...tes performance of VRLA battery is bad it s liable to cause thermal run away when heat accumulates Please improve ventilation and temperature condition when room temperature is high The distances betw...

Страница 10: ...ging time reached 16 hours Recharging Procedure 1 Connect the batteries in series with cables or copper bars and make sure that all the screws tightened with each joint then connect the positive of ba...

Страница 11: ...capacity if it is still less than 80 of rated capacity then the battery already fails Charging Equipment and Tools No Tool Explanation Purpose 1 Battery Test Equipment or Power System If there is no...

Страница 12: ...ge is lower than 2 08V cell or have been stored for long time the batteries should be charged to avoid damage caused by self discharge Storage temperature Longest interval over 30 once 6 months under...

Страница 13: ...ound Quarterly Maintenance Yearly Maintenance Items Details Benchmarks Maintenance Items Details Benchmarks Maintenance Float voltage for each battery Measure the voltage of each battery under floatin...

Страница 14: ...ow or not compensate according to temperature the battery system will in an insufficient charge state for a long period of time When the electricity is out the battery may not be able to work because...

Страница 15: ...me after discharge If the battery is put aside without charge for a long time after discharge it will affect the capacity and life of the battery Because in the negative some large size PbSO4 will be...

Страница 16: ...nner wall of the equipment and other batteries should be avoided 2 5 Keep the battery away from heating things such as a transformer 3 Installation and Wiring 3 1 Wrap the metal mounting tool such as...

Страница 17: ...lgroup com Tel 51 12 719445 www tempelgroup com Tempel Group en el mundo BARCELONA MADRID VALENCIA BILBAO SEVILLA LISBOA PORTO BUENOS AIRES LIMA SANTIAGO DE CHILE BOGOT SA PAULO M XICO DF CIUDAD DE PA...

Отзывы: