11. 3-way cooling valve
Use the RO12 port as the output port for the 3-way cooling valve
Logic:
In heating or hot water mode, OFF signal is sent. In cooling mode, ON signal is sent
12.1. Schematic of the mainboard
12.2. Smart Grid Ready=1
Utilization of a single potential-free contact:
12. SG Ready
SG-2
Smart Grid Ready=1
Open
Normal mode
Closed
Mode 4