background image

 Page 21 

SPECIAL CONSIDERATIONS FOR EXTREME 
WEATHER
If the unit is exposed to heavy wind:

Install unit so that air outlet fan is at a 90° 
angle to the direction of the wind. If needed, 
build a barrier in front of the unit to protect it 
from extremely heavy winds.
See 

Fig. 4.2

 and 

Fig. 4.3

 below.

Strong wind

Strong wind

Strong wind

If the unit is frequently exposed to heavy 
rain or snow:

Build a shelter above the unit it to protect 
it from the rain or snow.  Be careful not to 
obstruct air flow around the unit.

If the unit is frequently exposed to salty air 
(seaside): 

Use outdoor unit that is specially designed to 
resist corrosion.

Step 2: Install drain joint

Heat pump units require a drain joint. Before 
bolting the outdoor unit in place, you must install 
the drain joint at the bottom of the unit. Note 
that there are two different types of drain joints 
depending on the type of outdoor unit.

If the drain joint comes with a rubber seal

 

(see 

Fig. 4.4 - A

), do the following:

1.   Fit the rubber seal on the end of the drain joint 

that will connect to the outdoor unit.

2.   Insert the drain joint into the hole in the base 

pan of the unit.

3.   Rotate the drain joint 90° until it clicks in place 

facing the front of the unit.

4.   Connect a drain hose extension (not included) 

to the drain joint to redirect water from the 
unit during heating mode.

If the drain joint doesn’t come with a rubber 
seal

 (see 

Fig. 4.4

 

- B

), do the following:

1.   Insert the drain joint into the hole in the base 

pan of the unit. The drain joint will click in 
place.

2.   Connect a drain hose extension (not included) 

to the drain joint to redirect water from the 
unit during heating mode.

Seal

Drain joint

(A)

(B)

Base pan hole of

outdoor unit

Seal 

 IN COLD CLIMATES 

In cold climates, make sure that the drain hose 
is as vertical as possible to ensure swift water 
drainage. If water drains too slowly, it can 
freeze in the hose and flood  the unit.

Fig. 4.2

Fig. 4.3

Fig. 4.4

Outdoor Unit 

Installation

Wind Baffle

21

kaisai.com

Содержание FIREWIND Series

Страница 1: ...WALLTYPE INSTALLATION MANUAL FIREWINDSERIES...

Страница 2: ...piping 14 5 Connect drain hose 15 6 Connect signal cable 17 7 Wrap piping and cables 18 8 Connect indoor power wire 18 9 Mount indoor unit 18 Outdoor Unit Installation 20 8 1 Select installation locat...

Страница 3: ...s Refrigerant Piping 25 1 Cut pipe 25 2 Remove burrs 26 3 Flare pipe ends 26 4 Connect pipes 27 Air Evacuation 29 1 Evacuation Instructions 29 2 Note on Adding Refrigerant 30 Electrical and Gas Leak C...

Страница 4: ...rigeration cycle This can cause explosion and injury Do not allow children to play with the air conditioner Children must be supervised around the unit at all times 1 Installation must be performed by...

Страница 5: ...electric heater do not install the unit within 1 meter 3 feet of any combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumul...

Страница 6: ...er holder Dry battery AAA LR03 Air freshening filter Seal Drain joint Mounting plate 1 Accessories The air conditioning system comes with the following accessories Use all of the installation parts an...

Страница 7: ...installing or operating your new air conditioning unit Make sure to save this manual for future reference Installation Manual Aurora Series All Model Numbers INVERTER SPLIT TYPE ROOM AIR CONDITIONER...

Страница 8: ...tach Mounting Plate Page 12 Drill Wall Hole Page 12 Installation Summary Indoor Unit 2 Installation Overview Determine Wall Hole Position Page 12 1 2 3 4 12cm 4 75in or more 2 3m 90 55in or more 12cm...

Страница 9: ...Page 9 Mount Indoor Unit Page 18 STEP 8 Wrap Piping and Cable Page 18 L N S Connect Piping Page 25 Connect Wiring Page 17 Prepare Drain Hose Page 14 5 6 7 8 9 Installation Overview 9 kaisai com...

Страница 10: ...tual shape of your indoor unit may be slightly different The actual shape shall prevail Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Control Some Units Drainage Pi...

Страница 11: ...rong enough to support the weight of the unit A location at least one meter from all other electrical devices e g TV radio computer DO NOT install unit in the following locations Near any source of he...

Страница 12: ...l by tightening the screws directly into the clip anchors Step 3 Drill wall hole for connective piping You must drill a hole in the wall for refrigerant piping the drainage pipe and the signal cable t...

Страница 13: ...plate Recommended position of wall hole both to the left and right of mounting plate Relative distances between screw holes Indoor Unit Installation Fig 3 2 Correct orientation of Mounting Plate 85mm...

Страница 14: ...ifficult to remove by hand Knock out Panel 3 Use scissors to cut down the length of the insulating sleeve to reveal about 15cm 6in of the refrigerant piping This serves two purposes To facilitate the...

Страница 15: ...ll amount of water into the drain pan to make sure that water flows from the unit smoothly NOTE ON DRAIN HOSE PLACEMENT Make sure to arrange the drain hose according to Fig 3 5 DO NOT kink the drain h...

Страница 16: ...mes the maximum current of the unit 6 If connecting power to fixed wiring a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1 8in 3mm must be incorporated...

Страница 17: ...designed with a fuse to provide overcurrent protection The specifications of the fuse are printed on the circuit board such as T3 15A 250VAC T5A 250VAC etc 1 Prepare the cable for connection a Using...

Страница 18: ...ntertwine or cross the signal cable with any other wiring 2 Using adhesive vinyl tape attach the drain hose to the underside of the refrigerant pipes 3 Using insulation tape wrap the signal wire refri...

Страница 19: ...3 Connect drain hose and refrigerant piping refer to Refrigerant Piping Connection section of this manual for instructions 4 Keep pipe connection point exposed to perform the leak test refer to Elect...

Страница 20: ...rt the unit and will not vibrate Noise from the unit will not disturb others Protected from prolonged periods of direct sunlight or rain DO NOT install unit in the following locations Near an obstacle...

Страница 21: ...tdoor unit If the drain joint comes with a rubber seal see Fig 4 4 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain joint...

Страница 22: ...bolt 5 Hammer expansion bolts into the pre drilled holes 6 Remove the nuts from expansion bolts and place outdoor unit on bolts 7 Put washer on each expansion bolt then replace the nuts 8 Using a wren...

Страница 23: ...s and must be installed by a licensed electrician 2 All electrical connections must be made according to the Electrical Connection Diagram located on the side panels of the indoor and outdoor units 3...

Страница 24: ...ARNING ALL WIRING MUST PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIRGRAM LOCATED INSIDE THE OUTDOOR UNIT S WIRE COVER 2 Unscrew the electrical wiring cover and remove it 3 Unscrew the cable cla...

Страница 25: ...onditioner 15 000 25 82ft 10 33ft 15 000 and 24 000 30 98 5ft 20 66ft 24 000 and 36 000 50 164ft 25 82ft 36 000 and 60 000 65 213ft 30 98 5ft Connection Instructions Refrigerant Piping Step 1 Cut pipe...

Страница 26: ...PVC tape to prevent foreign materials from entering the pipe 2 Sheath the pipe with insulating material 3 Place flare nuts on both ends of pipe Make sure they are facing in the right direction becaus...

Страница 27: ...500 11lb ft 1 600 11 8lb ft 9 52 0 375 2 500 18 4lb ft 2 600 19 18lb ft 12 7 0 5 3 500 25 8lb ft 3 600 26 55lb ft 16 0 63 4 500 33 19lb ft 4 700 34 67lb ft DO NOT USE EXCESSIVE TORQUE Excessive force...

Страница 28: ...sing a spanner grip the body of the valve Do not grip the nut that seals the service valve See Fig 5 10 USE SPANNER TO GRIP MAIN BODY OF VALVE Torque from tightening the flare nut can snap off other p...

Страница 29: ...er holder Dry battery AAA LR03 Air freshening filter Seal Drain joint Mounting plate 1 Accessories The air conditioning system comes with the following accessories Use all of the installation parts an...

Страница 30: ...pes between the indoor and outdoor units are connected properly in accordance with the Refrigerant Piping Connection section of this manual Check to make sure all wiring is connected properly Evacuati...

Страница 31: ...ressure by hand You may tighten it further using a torque wrench if needed OPEN VALVE STEMS GENTLY When opening valve stems turn the hexagonal wrench until it hits against the stopper Do not try to fo...

Страница 32: ...t immediately and call a licensed electrician to find and resolve the cause of the leakage Note This may not be required for some locations in the US WARNING RISK OF ELECTRIC SHOCK ALL WIRING MUST COM...

Страница 33: ...o turn it on 3 Press the MODE button to scroll through the following functions one at a time COOL Select lowest possible temperature HEAT Select highest possible temperature 4 Let each function run fo...

Страница 34: ...l return unit to normal operating temperature b Using insulation tape wrap the indoor refrigerant pipe connections that you left uncovered during the indoor unit installation process IF AMBIENT TEMPER...

Страница 35: ...Dispose of the appliance at designated municipal electronic waste collection facility When buying a new appliance the retailer will take back the old appliance free of charge The manufacturer will tak...

Страница 36: ...otice for product improvement Consult with the sales agency or manufacturer for details CS370I 12F 16122000002396 20150820 The design and specifications are subject to change without prior notice for...

Отзывы: