Fan Temperature Value

This is the section in which fan output activation value is entered. You may enter a value between 5 
and 85 

°C

. The value is setup to the required value by using the up and down key starting from the 

digit where the blue line is. Then left key is pressed and the blue underline moves next to the left 

digit. All values are entered in the same way by using up and downkeys. “Select”

 

key is pressed to 

take them into the memory.

“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into 

the memory.

1 9 3

Fan Settings

This is section in which the setup values of fan inputs are entered.

1 9 3 1

Fan Temperature Value (5 – 85 °C)

Fan Temperature Value

050

°C

050

°C

Save

Changes ?

The required condition is selected for function by using

up or down keys. “Select”

 

key is pressed to take them

into the memory. “Save changes?” message will appear

on the screen. Pressing “Okay” key, the value is taken into

the memory. 

1 9 3 2

 Fan Output

Apply

▲ +

▼ -

disable

Fan Output

1

3 4 5

7

9 10 11 12

2

6

8

1

3 4 5

7

9 10 11 12

2

6

8

1

3 4 5

7

9 10 11 12

2

6

8

1 9 4 6 4

Step Protection Function

De-activation of the capacitors is recommended to protect them against temperature, voltage and 

harmonics. This is the section in which protection is permitted. 

P.S.: In case the current connector moves out or there is a connection failure at the voltage inputs, 

protection is activated automatically and de-activates the steps one by one. 

1 9 4 1

This is the section in which the temperature protection function is 

activated or de-activated. The over temperature alarm should also 

be activated to operate the protection function (Chapter 19127).

The required condition is selected for function by using

up or down keys. “Select”

 

key is pressed to take them

into the memory. “Save changes?” message will appear

on the screen. Pressing “Okay” key, the value is taken into

the memory. 

Temperature Protection

Apply

▲ +

▼ -

Disable

Temperature Protection

1 9

Voltage Protection

Apply

▲ +

▼ -

Disable

Voltage Protection

4 2

1 9

Harmonics Protection

Apply

▲ +

▼ -

Disable

Harmonic Protection

4 3

This is the section in which the protection function is activated or de-

activated against voltage harmonics. Voltage harmonic alarms 

(THDV and/or HDV) should be activated in order to operate 

protection function.

The required condition is selected for function by using

up or down keys. “Select”

 

key is pressed to take them

into the memory. “Save changes?” message will appear

on the screen. Pressing “OK” key, the value is taken into

the memory. 

This is the section in which the voltage protection function is activated 

or de-activated. The voltage alarms should also be activated to 

operate the protection function (over voltage, under voltage, no 

phase).

The required condition is selected for function by using

up or down keys. “Select”

 

key is pressed to take them

into the memory. “Save changes?” message will appear

on the screen. Pressing “Okay” key, the value is taken into

the memory. 

1

3 4 5

7

9 10 11 12

2

6

8

1

3 4 5

7

9 10 11 12

2

6

8

1

3 4 5

7

9 10 11 12

2

6

8

Содержание VARko-112-TFT

Страница 1: ...VARko 112 TFT Reactive Power Control Relay Banks Markets Oil Stations Schools Workshops Hotels 12 Steps KAEL M hendislik Elektronik Tic ve San Ltd ti www kael com tr...

Страница 2: ...ing system is used in the micro processor Password protected Measuring temperature Following electrical parameters of three phases at the same time Voltage of phase V L N Current of phase I Cos value...

Страница 3: ...use the device for different purposes other than compensation system 6 Fix the device tightly on the control panel with the apparatus given on the device without hanging around 7 Do not interfere to t...

Страница 4: ...s always located on the top of the screen 8 LCD screen is used in VARko 112 TFT to provide it to be more easier in use and be intelligible In case the keys are not pressed for a long time the device s...

Страница 5: ...n mode In this case it is required to draw enough current from each phase If enough current can not be drawn from any phase the device warns as current flow direction not detected and shows the phase...

Страница 6: ...K7 K8 K9 K10 K11 K12 L2 L3 I1 k1 Voltage inputs Current Transformer Inputs Load Fuse compatible to the capacitor power ALR ALR Alarm output FAN Fan output FAN 2A 2A VARko 112 TFT 400V AC X 5A Main Sc...

Страница 7: ...ll the values are entered in the same way by using up and down keys Press Apply key inorder to take the period of step activating into memory Save changes message will appear on the screen When Okay k...

Страница 8: ...e entered The device directs the user with subcommand display continuously It is moved on the step of which the power is required to be entered by using the up and down keys In the meantime that line...

Страница 9: ...s given and device warns the user In this case capacitors and devices in the system may be damaged or may not be operated properly Voltage protection activated may be preferred in the step protection...

Страница 10: ...emoving the failure steps internalized zero should be internalized again 1 9 1 2 4 General Alarms Total Over Compensation enable In case of this alarm The system may be kept in penalty Review the capa...

Страница 11: ...ill appear on the screen Pressing Okay key the value is taken into the memory 170 Save changes In case voltage protection is activated in the step protection function Chapter 19112 all steps are de ac...

Страница 12: ...harmonic protection is activated in the step protection function Chapter 19118 all steps are de activated one by one to protect the capacitors when HDV setup value is exceeded 1 9 2 6 THD Current Set...

Страница 13: ...utomatically and de activates the steps one by one 1 9 4 1 This is the section in which the temperature protection function is activated or de activated The over temperature alarm should also be activ...

Страница 14: ...Enter New Password 0 Okay Exit Password active passive Change password 1 10 9 PASSWORD Re Enter New Password 0 Exit Password active passive Change password 1 10 9 PASSWORD Re Enter New Password 0 Oka...

Страница 15: ...Voltage 350V Alarm Setting Values Over Temperature 70 C Alarm Setting Values THD Voltage 4 Alarm Setting Values HD Voltage 4 Alarm Setting Values THD Current 30 Alarm Setting Values HD Current 30 Fan...

Страница 16: ...Terminal Protection Class IP 00 Environment Temperature 5 C 50 C Humudity 15 95 without condensation Connection Type On the front cover of the panel Dimensions 144x144x45 mm Technical Info 37 mm 140m...

Отзывы: