1 9 2
Alarm Setting Values
This is the section in which the alarm setup values are entered.
1 9 2 1
Over Voltage (420 – 500V)
Apply
▲ +
▼ -
◄
440
Cancel
Okay
Exit
Over voltage setting
V
Over voltage setting
V
This is the section in which the value of over voltage are entered. You may enter a value between
440 and 500 Volts. The value is setup to the required value by using the up and down key starting
from the digit where the blue line is. Then left key is pressed and the blue underline moves next
to the left digit. All values are entered in the same way by using up and downkeys. “Select”
key is
pressed to take them into the memory.
“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into
the memory.
440
Save
changes?
In case voltage protection is activated in the level protection function (Chapter 19111), all levels
are de-activated one by one to protect the capacitors when over voltage setup value is exceeded.
1 9 2 2
Under Voltage (300 – 380 V)
Apply
▲ +
▼ -
◄
170
Cancel
OK
ESC
Under voltage setting
V
Under voltage setting
V
This is the section in which the value of under voltage are entered. You may enter a value
between 300 and 380 Volts. The value is setup to the required value by using the up and down
key starting from the digit where the blue line is. Then left key is pressed and the blue underline
moves next to the left digit. All values are entered in the same way by using up and downkeys.
“Select”
key is pressed to take them into the memory.
“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into
the memory.
170
Save
changes?
In case voltage protection is activated in the step protection function (Chapter 19112), all steps are
de-activated one by one to protect the capacitors when under voltage setup value is exceeded.
The contactors are in difficulty to stay drawn especially under a certain voltage and, therefore the
capacitor as well as contactor are exposed to operate in undesirable overload and arc. For this
reason, activating voltage protection function is recommended.
Apply
▲ +
▼ -
◄
050
Cancel
Okay
Exit
Over Temp. alarm value
°C
This is the section in which the value of over temperature are entered. You may enter a value
between 5 ile 85
°C
. The value is setup to the required value by using the up and down key
starting from the digit where the blue line is. Then left key is pressed and the blue underline
moves next to the left digit. All values are entered in the same way by using up and downkeys.
“Select”
key is pressed to take them into the memory.
“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into
the memory.
In case the temperature exceeds
the setup value, the value
displayed in light blue color
becomes red on the upper right of
screen.
050
Over Temp. alarm value
°C
Save
Changes ?
In case temperature protection is activated in the step protection function (Chapter 19114), all
steps are de-activated one by one to protect the capacitors when over temperature setup value is
exceeded.
1 9 2 3
Over Temperature (5 – 85 °C)
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8