General Informations

The device measures the True RMS value of the voltage and frequency in 
mono phase systems accurately. 
It is possible to observe the voltage value in the upper screen and the 
frequency value in the buttom screen simultaneously. 
The device contains many protections as followes:
■ Over Voltage protection.
■ Under voltage protection:
■ Over frequency protection.
■ Under frequency protection.
As the device is beeing installed it closes its output contact if the voltage and 
frequency values are within the adjusted ranges. In case of any previous 
mentioned faults the the device opens its output contact at the end ofdelay 
adjusted by user. When the values return withiin the adjusted ranges the 
device closes its output contacts at the end of an adjusted delay.

V

Re

t

t

t-1

(o-U)

(u-U)

t-3

t-1

t-3

Umax

Umin

L1,L2,L3

Normal

Normal

Over&Under Voltage : (o-U) (u-U)

Over voltage (o-U), it can be adjusted between Umax= (230 – 290 V). 
Under voltage (u-U), it can be adjusted between Umin=(150 – 210 V). 
■ If the voltage drops below the adjusted under voltage limit then 

u-U

 shows on 

the screen and the device closes it output contact after t-1 delay. 
■ If the voltage exceeds the adjusted over voltage limit then 

o-U

 shows on the 

screen and the device closes it output contact after t-1 delay.  
The hysteresis value is 6V.

 

Locking Property :

It can be controlled by two parameters; Locking Time and Locking Counter. 
If the number of openning reaches the adjusted locking counter within the 
adjusted locking time then the device opens its output contact and locks its 
functions until the user pressed 

Reset 

button.

 

If the locking counter is adjusted 

to 

oto

 then this function is inactive and the device never locks itself

L-t : Locking Time 

( 001 – 060 minutes )

It is well known the the frequentely occuring faults may damage the system. For 
that the device locks itself when the number of faults reaches the adjusted 
locking number within this locking time. This way the sistem is protected and the 
user has the chance to investigate the problem.

L-C : Locking Counter 

( oto , 001 – 010 )

The number of the faults allowed within the period L-t. If the number of the faults 
exceeds this adjusted counter value then the device locks itself. The user must 
press Reset button agter the fault passes in order to unlock the device. If L-C is 
set to 

oto 

then this property is inactive.

Over and/or Under Frequency Protection : ( 40 – 70 Hz )

Under frequency can be adjusted be tween  (u-F) = 40 Hz .......[(o-F)-0,4]  
Over frequency can be adjusted between (o-F)   = [(u-F) + 0,4]..... 70 Hz.
It is possible to activate one or two of these protections or deactivate them 
both.
■ If o-F = 55 Hz and u-F = oFF  then the device protects from over frequency 
( if the frequency exceeds 55hz then the device shows 

o-F

 on the buttom 

screen and opens its output contact at the end of t-2 delay).
■ If o-F = oFF and u-F = 45 Hz then the device protects from under frequency 
( if frequency drops below 45Hz then the device shows 

u-F

 on the buttom  

screen and opens its output contact at the end of t-2 delay).
■ If o-F = oFF and u-F = oFF then the frequency protection is disabled.

Parameters :

The menu where protection functions are adjusted. To enter this menu press 
set button until set is shown on the nuttom screen. Parameters are as follow:

► o-U : Over Voltage Adjustment 

( 230 V – 290 V )

If the phase – phase voltage exceeds the adjusted value then the 
device opens it output contacts at the end of t – 1 delay. 

► u-U : Under Voltage Adjustment 

( 150 V – 210 V)

If the phase – phase voltage drops below the adjusted value then 
the device opens it output contacts at the end of t – 1 delay. 

► t-1 : Openning Delay (Voltage) 

( 00,1 – 99,9 seconds)

If any of voltage faults occurs, and if it lasts for t-1 period then 
the device opens its output contact.

► t-2 : Openning Delay (Frequency)

( 00,1 – 99,9 seconds)

If any of freuqency faults occurs, and if it lasts for t-2 period 
then the device opens its output contact.

► t-3 : Returning Delay (Voltage and Frequency)

( 00,1 – 99,9 seconds)

To close the output contact after openning because of both 
voltage and frequency faults, the values should return to the 
normal ranges and after t-3 delay the device closes its output 
contact.

► L-t : Locking Time 

( 001 – 060 minutes )

The device locks itself when the number of faults reaches the 
adjusted locking number within this locking time. This way the 
sistem is protected and the user has the chance to investigate 
the problem.

► L-C : Locking Counter 

( oto , 001 – 010 )

The number of the faults allowed within the period L-t. If the 
number of the faults exceeds this adjusted counter value then the 
device locks itself. The user must press Reset button agter the 
fault passes in order to unlock the device. If L-C is set to 

oto 

then this property is inactive.

► o-F : Over Frequency Adjustment

It can be set between (o-F) = [(u-F) + 0,4]..... 70 Hz. 
If it is set to o-F = oFF then this protection is disabled.

► u-F : Under Frequency Adjustment 

It can be set between (u-F)  = 40 Hz .......[(o-F) – 0,4] .
If it is set to u-F = oFF then this protection is disabled.

► qut : Quit

If Set button is pressed there then the device goes back to the 
measurement screen.

Under Voltage

Over Voltage

V

Re

t

t

(o-U)

(u-U)

t-3

Over Voltage
   1. Fault

L1,L2,L3

Normal

Normal

If: L-C (Locking counter)   = 2 
     L-t   (Locking time) = 3 minutes

t-1

t-1

t-3

Reset Button is pushed
and locking is ended.

Locking Occurs

< 3 Minutes

Over Voltage
   2. Fault

Re

t

t

t-2

(o-F)

(u-F)

t-3

t-2

t-3

55 Hz

45 Hz

Under Frequency

Over Frequency

L1,L2,L3

Normal

Normal

f(Hz)

DV – 72 - 

01C

®

DIGITAL VOLTAGE & FREQUENCY MONITORING
DEVICE
►  True RMS

TECHNICAL DATA:

Rated Voltage (Un)

: 220Vac (L1-N)

Operating Range

: (0,8-1,1) x Un

Frequency

: 50 / 60 Hz

Supply Pow er Consumption

: < 4VA

Measurement  Pow er 
Consumption

: <1VA 

Voltage Measurement

: 10 – 500 Vac

Frequency Measurement

: 40 / 100 Hz

Measurement Sensitivity

: %1±1 digit

Measurement Catagory

: CAT III

Display

: 3 Digit x 2 line LED

Contact Current

: Max. 5A / 240Vac

Protection Class

: IP 20

Connector Protection Class

: IP 00

Temperature

: - 5 °C .... + 50 °C

Humidity

: %15 ...... %95 

  

  (w ithout condensation)

Connection Type

: To front panel tap

Dimensions

: 72x72x80 mm