7.3
Surveying the connection area
1
5
3
4
2
6
Fig. 22:
Connection area on DC side (left) / AC side (right)
1
5
3
4
2
6
Fig. 23:
Connection area (XL - Version)
Legend
1
AC connection point
4
DC connection point
2
AC overvoltage protection base
5
DC overvoltage protection
3
AC earthing bolt
6
PID connection point
7.4
Making the electrical connections
NOTE
Select conductor cross-section, safety type and safety value in accordance with the following basic condi-
tions:
Country-specific installation standards; power rating of the device; cable length; type of cable installation;
local temperature
NOTE
All electrical installations must be carried out in accordance with local electrical standards and conform
to the National Electrical Code® ANSI / NFPA 70 or the Canadian Electrical Code® CSA C22.1.
This document does not replace any local, federal or national laws, regulations or regulations that apply to
the installation and use of the product, and is not intended to replace them, including the applicable elec-
trical safety regulations.
All installations must conform to the laws, regulations and standards that are applicable in the country of
installation. KACO new energy does not assume any responsibility for compliance or lack of compliance
with such laws or codes in connection with the installation of the product.
7.4.1
Supply line and fuse requirements
DC-side
Max. cable cross-section
450 kcmil
Min. cable cross-section
acc. to local installation standards
Diameter of cable for cable fitting
0,63 - 1,10 inch
Cable lug dimension b width max.
1,65 inch
Length of insulation to be stripped off
Depending on the ring cable lug
Recommended cable type
solar cable
Cable lug Ø connection bolt
Bore for M10 screw
Tightening torque
265.50 In-Ibs
Fitting for DC connection
M40
Torque for cable fitting
65 In-Ibs
AC-side
Max. cable cross-section
450 kcmil
Min. cable cross-section
acc. to local installation standards
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3