7.9.6
Connecting "Inverter Off"
Connect the Powador-protect (only in the case of 380/400V
blueplanet 87.0TL3 / 92.0TL3)
↻
The cable to the external grid protection device is available on the device.
↻
Cover of the device has been opened.
1 Loosen the cable fittings [ W_19]
2 Thread the connection cables through the cable fittings.
3 Connect wire A (+) to the terminal marked "INV OFF+" on the first device via the
"DO1" terminal of the protective device.
4 Connect wire B (-) to the terminal marked "INV OFF-" on the first device via the
"GND" terminal of the protective device.
5 Connect the other devices to one another as follows:
- Wire A (+) to wire A (+) and wire B (-) to wire B (-).
6 Tighten cable fitting [ W_19 / 22 In-Ibs ]
7 After commissioning: Configure the
external
Overvoltage protection
Powador-protect in the menu entry
Properties / Functions
Proper-
ties / functions.
RS485
B
A
GND
B
A
GND
-
D01
GND
4
3
2
1
RS485
B
A
GND
B
A
GND
-
+
INV
OFF
INV
OFF
+
1
2
x
x
y
y
INV Signal
Powador-
protect
A
B
A
B
Fig. 38:
Connect the device to
Powador-protect
Connect the external device
↻
The cable to the external grid protection device is available on the device.
↻
Cover of the device has been opened.
1 Loosen the cable fittings [ W_20]
2 Thread the connection cables through the cable fittings.
3 Connect wire A (+) from "COM" (11) on the terminal of the protective device to
the terminal marked "INV OFF+" on the first device.
4 Connect wire B (+) from "NC" (12) on the terminal of the protective device to
the terminal marked "INV OFF-" on the first device.
5 Connect the other devices to one another as follows:
- Wire A (+) to wire A (+) and wire B (-) to wire B (-).
6 Tighten cable fitting [ W_20 / 13,27 In-Ibs ].
7 After commissioning: Configure the
external
Overvoltage protection exter-
nal device in the menu entry Properties / Functions Properties / functions.
RS485
B
A
GND
B
A
GND
-
14 NO
24
21
RS485
B
A
GND
B
A
GND
-
+
INV
OFF
INV
OFF
+
1
2
min./ max.
10-24V(+/-20%)
/15mA-1A
x
x
y
y
12 NC
11 COM
22
INV OFF
INV ON
External
device
A
B
A
B
Fig. 39:
Connecting the device to
the external grid protection device
7.10
Sealing the connection area
↻
The grid connection has been prepared.
1 Lift the housing cover onto the housing and loosely tighten the fastening screws.
2 Secure the housing cover by tightening all 6 screws in a diagonally opposite se-
quence [ T_25
/
42.48 In-Ibs ].
»
The device has been mounted and installed.
»
Put the device into operation.
2
1
Fig. 40:
Closing the housing cover
1
Housing cover
3
Screws
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 33
EN-US