DC-side
Diameter of cable for cable fitting
0,63 - 1,10 inch
Cable lug dimension b width max.
1,65 inch
Length of insulation to be stripped off
Depending on the ring cable lug
Recommended cable type
Solar cable
Cable lug Ø connection bolt
Bore for M10 screw
Tightening torque
265.50 In-Ibs
Fitting for DC connection
M40
Torque for cable fitting
65 In-Ibs
AC-side
Max. cable cross-section
450 kcmil
Min. cable cross-section
acc. to local installation standards
Diameter of cable for cable fitting
0,63 - 1,10 inch
Length of insulation to be stripped off
Depending on the ring cable lug
Cable lug Ø connection bolt
Bore for M10 screw
Tightening torque
265.50 In-Ibs
Connection type
Cable lug
Cable lug dimension w - maximum width
1,65 inch
Ground conductor connection
M10
Ground conductor connection tightening torque
88.5 In-Ibs
Electrical protection in installation (provided by the customer)
250A (preliminary)
Fitting for AC connection
M40
Torque for cable fitting
65 In-Ibs
Interfaces
Diameter of cable for cable fitting
(2x) 0,31 - 0,67 inch
Torque for cable fitting
44.25 In-Ibs
RS485 connection type
spring-type terminal
RS485 terminal cable cross-section
23 - 15 AWG
Diameter of cable for cable fitting
(3x) 0,19 - 0,39 inch
Torque for cable fitting
22 In-Ibs
Ethernet connection type
RJ45
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 20