Instruction manual Kabola KB-Series version 6, 2018
23
Appendix C Troubleshooting
Listed below you will find a list with possible problems, their reasons and solutions. When you encounter
problems not listed, you should contact your dealer.
Never try to solve problems on your own.
Problem
Possible reason
Possible solution
Burner will not start
Oil supply interrupted
Maximal thermostat
Bleed the oil filter
Change contaminated filter element
Fill the oil tank
Reset the maximal thermostat
Power supply interrupted
Check the fuses (4-8A)
Check the power supply
Shut down power supply, and
disconnect the photo cell, switch
power on and when burner starts
connect the photo cell.
Burner stops
Reset burner (once)
Flame protection dirty (photo cell)
Clean glass of flame protection
Flame protection defect
(photo cell)
Replace flame protection
Burner starts pulsing
Flue gas flow interrupted
Clear chimney opening
Boiler dirty
Clean boiler
Oil supply interrupted
See above
Nozzle defective
Replace nozzle
Burner shows error
Reset burner (once)
Low voltage
Check voltage level
Press the reset button for more
than 3 seconds
2 blinks, alarm on terminal 10
No establishment of flame at the
end of safety time
Faulty or soiled fuel valves
Faulty or soiled flame detector
Poor adjustment of burner, no fuel
Faulty ignition equipment
3x blinks, alarm on terminal 10
Free
4 blinks, alarm on terminal 10
Extraneous light on burner startup
5 blinks, alarm on terminal 10
Free
6 blinks, alarm on terminal 10
Free
7 blinks, alarm on terminal 10
Too many losses of flame during
operation (limitation of repetitions)
Faulty or soiled fuel valves
Faulty or soiled flame detector
Poor adjustment od burner
8 x blinks, alarm on terminal 10
Time supervision oil preheater
Oil preheater failed 5 times during
prepurging
9 blinks, alarm on terminal 10
Free
10 blinks
Wiring error or internal error, output
contacts, other fault
Press the lockout reset button for
about 1-3 sec to reset burner
Oil supply interrupted
See above
Boiler does not react to thermostat
Wire in main connector has not
been removed (room thermostat)
Remove wire from main connector
between T1 and T2
Boiler thermostat incorrectly
adjusted
Adjust boiler thermostat
Battery of room thermostat flat
Replace battery
Water is not circulating
Pump couplings are closed
Open pump couplings
Pump not connected to electricity
supply
Connect pump
Rotor of pump is stuck
Turn pump with your hand (see
pump manual)
When problems with the boiler will not disappear, call an engineer from Kabola.
Содержание Ecoline series
Страница 1: ...User manual KB ECOLINE series English Ecoline serie CH Calorifier Combi...
Страница 20: ...Instruction manual Kabola KB Series version 6 2018 20 Appendix A Technical specifications...
Страница 21: ...Instruction manual Kabola KB Series version 6 2018 21 Appendix B Electrical diagram 230 V...
Страница 22: ...Instruction manual Kabola KB Series version 6 2018 22 Appendix B Electrical diagram 230 V...
Страница 24: ...Instruction manual Kabola KB Series version 6 2018 24 Appendix D Boiler parts model 2012 2016...
Страница 28: ...Instruction manual Kabola KB Series version 6 2018 28 Spareparts list model 2016 2017...
Страница 30: ...Instruction manual Kabola KB Series version 6 2018 30 Appendix F CE declaration...
Страница 31: ...Instruction manual Kabola KB Series version 6 2018 31 Warranty Conditions...
Страница 32: ...Instruction manual Kabola KB Series version 6 2018 32 Appendix G Guarantee conditions...