DHW heating
6 720 645 817
(2010/09)
71
Specification
T
Sp
Cylinder temperature
T
Z
DHW outlet temperature
Constant DHW output
The constant outputs shown refer to the following
parameters:
•
Flow temperature 90 °C
•
Outlet temperature 45 °C
•
Cold water inlet temperature 10 °C
•
Maximum heat input (heat source input at least the
same as the cylinder coil output)
Reducing the specified heat input will result in a
reduction in the constant output and the performance
factor (N
L
).
Cylinder type
Unit
SE 300-1
Heat exchanger
Heat transfer
–
Indirect coil
Number of coils
–
–
Available capacity
l
288
Heating water content
l
–
Heating surface
m
2
0.93
Performance factor N
L
1)
to DIN 4708 at max. output
1) The performance factor N
L
corresponds to the number of residential units to be supplied, each with 3.5 occupants, one standard
bath tub and two further draw-off points.
–
11.5
Further details
Available amount of DHW (without reheating)
2)
T
Sp
= 60 °C and
- T
Z
= 45 °C
- T
Z
= 40 °C
2) Distribution losses outside the cylinder have not been taken into account.
l
l
441
–
Standby loss (24 h) to DIN 4753 part 8
2)
kWh/d
1.92
Maximum operating pressure, water
bar
10
Maximum operating pressure, heating
bar
15
Weight (empty, excl. packaging)
kg
50
Colour
–
White
Tab. 39