CAUTION:
Do not let fiber-optic cables hang free from the connector. Do
not allow the fastened loops of a cable to dangle, which stresses the cable
at the fastening point.
Figure 79: Attaching a Cable to a DPC
Fiber-optic cable
connector
Figure 80: Attaching a Cable to a MIC
g004928
Fiber-optic cable
Connecting the Alarm Relay Wires to the MX480 Craft Interface
To connect the alarm relay wires between a router and an alarm-reporting device (see
1.
Prepare the required length of replacement wire with gauge between 28-AWG and
14-AWG (0.08 and 2.08 mm
2
).
2.
Insert the replacement wires into the slots in the front of the block. Use a 2.5-mm
flat-blade screwdriver to tighten the screws and secure the wire.
3.
Attach an ESD grounding strap to your bare wrist and connect the strap to one of the
ESD points on the chassis.
219
Copyright © 2019, Juniper Networks, Inc.
Chapter 3: Initial Installation and Configuration
Содержание MX480
Страница 14: ...Copyright 2019 Juniper Networks Inc xiv MX480 Universal Routing Platform Hardware Guide...
Страница 22: ...Copyright 2019 Juniper Networks Inc xxii MX480 Universal Routing Platform Hardware Guide...
Страница 138: ...Copyright 2019 Juniper Networks Inc 138 MX480 Universal Routing Platform Hardware Guide...
Страница 168: ...Copyright 2019 Juniper Networks Inc 168 MX480 Universal Routing Platform Hardware Guide...
Страница 352: ...Copyright 2019 Juniper Networks Inc 352 MX480 Universal Routing Platform Hardware Guide...
Страница 382: ...Copyright 2019 Juniper Networks Inc 382 MX480 Universal Routing Platform Hardware Guide...
Страница 420: ...Copyright 2019 Juniper Networks Inc 420 MX480 Universal Routing Platform Hardware Guide...