Table 66: FRU DC Power Requirements (continued)
Maximum Power Requirement
Model Number
Component
•
When installed into MPC8E:
1.250 A @ 48 V (60 W)
•
When installed into MPC9E:
1.771 A @ 48 V (85 W)
MIC-MRATE
MIC MRATE
36 W at 55° C
35 W at 40° C
34 W at 25° C
MIC-3D-8DS3-E3
MIC-3D-8CHDS3-E3-B
DS3/E3 MIC
33.96 W
MIC-3D-4COC3-1COC12-CE
Channelized OC3/STM1
(Multi-Rate) Circuit Emulation
MIC with SFP
RELATED DOCUMENTATION
MX2010 Power System Description | 95
Connecting Power to a DC-Powered MX2010 Router with Power Distribution Modules (-48 V) | 304
MX2010 DC Power (-48 V) System Electrical Specifications | 201
MX2010 DC Power Distribution Description (-48 V) | 197
MX2010 DC Power Distribution Description (-48 V)
Most sites distribute DC power through a main conduit that leads to frame-mounting DC power distribution
panels, one of which might be located at a location near the rack that houses the router. A pair of cables
(one input and one return) connects each set of PDM input terminal studs to the power distribution panel.
The PSMs can be connected to two separate feeds from different sources that are used for feed redundancy.
There are two PDMs located in slots PDM0/Input0 and PDM1/Input1 that are capable of carrying seven
to nine feeds each. Each feed is connected from one source to one PDM and feeds from the other source
to the second PDM of the DC power system. This configuration balances power draw for the system by
using the commonly deployed A/B feed redundancy.
Each system provides N+1 PSM redundancy along with N+N feed redundancy. If both DC feeds are
available, operating power draws from the feed with higher voltage. These feeds are set by the input mode
DIP switch located on the DC PSM (see
“MX2010 DC Power Supply Module (-48 V) Description” on
197
Содержание MX2010
Страница 1: ...MX2010 Universal Routing Platform Hardware Guide Published 2019 12 03...
Страница 28: ......
Страница 30: ...MX2010 Power System Description 95 MX2010 Cooling System Description 45 4...
Страница 54: ...MX2010 Router Overview 3 MX Series Router Interface Names MX2010 Port and Interface Numbering 90 28...
Страница 144: ...MX2010 DC Power 48 V System Electrical Specifications 201 122...
Страница 146: ......
Страница 233: ......
Страница 258: ...Figure 85 Removing an AC Power Distribution Module Before Installing the MX2010 Router D g007439 241...
Страница 259: ...Figure 86 Removing a DC Power Distribution Module 48 V Before Installing the MX2010 Router D g007431 242...
Страница 273: ...Figure 98 Loading the MX2010 Router into the Rack g007436 256...
Страница 294: ...Figure 113 Reinstalling an AC Power Distribution Module g007440 D 277...
Страница 295: ...Figure 114 Reinstalling a DC Power Distribution Module 48 V D g007432 278...
Страница 373: ...4 PART Installing and Replacing Components Installing Components 359 Replacing Components 429...
Страница 374: ......
Страница 620: ......
Страница 715: ...6 PART Troubleshooting Hardware Troubleshooting Components 703...
Страница 716: ......
Страница 744: ......
Страница 767: ...Remove the shipping brackets and hardware and set them aside Guide the router in the shipping crate 754...
Страница 772: ......
Страница 775: ...763...
Страница 783: ...772...
Страница 796: ...Jewelry Removal Warning 787...
Страница 799: ...Operating Temperature Warning 790...
Страница 808: ...DC Power Disconnection Warning 799...
Страница 812: ...DC Power Wiring Sequence Warning 803...
Страница 815: ...DC Power Wiring Terminations Warning 806...