(1)
(16)
(15)
Figure 4: Installation in panel-mounted housing
o
Install panel-mounted housing in the correct position in the wall.
o
Pull the connecting cables through the designated bushings.
DANGER!
Electrical shock when live parts are touched. The mains voltage and low
voltage are located in a shared appliance box. If there is an error, other
connected components may carry mains voltage.
Electrical shocks can be fatal.
Always secure the mains voltage with the enclosed tube.
Run the cables so that low voltage wires are securely protected against mains
voltage.
o
Strip the mains voltage cable to the length of the enclosed tube.
o
Pull the supplied tube over the stripped mains voltage wires
L
and
N
.
o
Connect the mains voltage
L
and
N
to terminal (7).
o
Connect the KNX bus line to terminal (8).
o
Connect Ethernet cable to the Ethernet connection (14).
o
Install device in panel-mounted housing (15). Observe the labelling
OBEN TOP
. Use the
screws (16) supplied.
o
Remove protective film from the touchscreen surface (2).
o
Attach and press on the design frame (1) in the correct position.
Removing the Design frame
o
Remove the design frame from the device on both sides with your fingers. To prevent
damage to the frame, do not use any tools.
Restarting the device
The device can be restarted without voltage interruption by using the reset buttons.
i
Data that was not saved beforehand could be lost (e.g. data of the datalogger).
o
Briefly press the reset button on the front side (4) or rear side (12) of the device.
The device is restarted after approx. 1 minute.
5.2 Commissioning
Load physical address
o
Press the programming button (10).
4/6
82590203
J:0082590203
24.11.2014
Smart Panel 5.1 KNX