Assigning additional physical addresses
Additional physical addresses can be assigned manually with ETS or automatically by the
device itself.
o
Press the programming button (9) for approx. 5 seconds.
The programming LED flashes.
The device checks the physical addresses present in the line and selects the required free
physical addresses.
o
Determine the physical addresses occupied by the device and insert them in the ETS
project as dummy devices.
i
When additional bus devices are added, the corresponding physical addresses can be
assigned twice. Delete the additional physical addresses – press the programming button
(9) for approx. 10 seconds – and assign them again.
5 Appendix
5.1 Technical data
Power over Ethernet supply
Power over Ethernet
IEEE802.3af
Rated voltage
DC 48 V
Power consumption
max. 0.8 W
External supply
Rated voltage
AC 12 ... 24 V SELV
Rated voltage
DC 12 ... 30 V SELV
Power consumption
max. 1.7 W
Connection of power supply
Connection terminal
Ambient conditions
Ambient temperature
-5 ... +45 °C
Storage/transport temperature
-25 ... +70 °C
Safety class
III
Relative humidity
5 ... 93 % (No moisture condensation)
Fitting width
36 mm / 2 modules
Weight
approx. 100 g
Network communication
IP communication
Ethernet 10BaseT
IP transmission rate
10 Mbit/s
IP connection mode
RJ45 socket
Protocols
ARP, ICMP, IGMP, UDP/IP, DHCP
KNXnet/IP
Core, Routing, Tunneling, Device Management
KNX
KNX medium
TP 1
Commissioning mode
S mode
Rated voltage KNX
DC 21 V ... 32 V SELV
Connection mode KNX
Connection terminal
Current consumption KNX
max. 10 mA
4/5
82561723
J:0082561723
16.03.2010
KNX IP router