Technical Data
Technical Data
Switching actuator outputs, 6-channel and 8-channel
(outputs A5 – A8)
Switched voltage
: 230 V AC
Switched current at 230 V AC
: 6 A / AC1
Switching capacity
incandescent lamps
: 1000 W
fluorescent lamps
non-compensated, cos
ϕ
= 0.5
: 500 W
parallel compensation, cos
ϕ
= 1 : 2 x 58 W / 14 µF
3 x 36 W / 14 µF
6 x 18 W / 14 µF
lead-lag circuit, cos
ϕ
= 1
: 1000 W
Siemens electronic ballast
58 W fluorescent lamp
: 10 units
36 W fluorescent lamp
: 15 units
18 W fluorescent lamp
: 15 units
GB
GB
4-channel C-load and and 8-channel C-load switching
actuator outputs
Switched voltage
: 230 V AC, 400 V AC
Switched current at 230 V AC
: 16 A / AC1; 10 A / AC3
Switched current at 400 V AC
: 10 A / AC1; 6 A / AC3
Switching capacity
incandescent, HV halogen lamps
: 3680 W
LV halogen lamps
: 2000 VA
Tronic transformers
: 2500 W
fluorescent lamps
non-compensated, cos
ϕ
= 0.5
: 3680 W
parallel compensation, cos
ϕ
= 1
: 2500 W / 200 µF
lead-lag circuit, cos
ϕ
= 1
: 2 x 3680 W
Mercury / sodium vapour lamp
non-compensated; parallel compensation
: 3680 W / 200 µF
Technical specifications subject to change