finely stranded without conductor sleeve

0.75 ... 4 mm²

Finely stranded with conductor sleeve

0.5 ... 2.5 mm²

Fitting width

72 mm / 4 modules

Bus line
Rated voltage

DC 12 V SELV

Current consumption

10 mA

Connection, Bus

Connection terminal

Cable length

max. 3 m

Measuring ranges per channel
Current

0 mA ... 16 A

Accuracy (current)

± 0.5 % of the current value and ± 8 mA

Voltage

207 ... 250 V

Accuracy (voltage)

± 0.5 % of curr. val.

Transmitted power and output values
Effective output

-4000 ... 4000 W

Apparent output

0 ... 4000 VA

Idle output

-4000 ... 4000 var

Accuracy (power)

± 0.5 % of the current value and ± 2 W/VA/var

Effective energy

-99999 ... 99999 kW·h

5.2 Parameter list

Settings window
Device settings

Parameters

Setting options, Basic
setting

Explanations

Manual commissioning

On, Off
Basic setting: On

Blocks manual commissioning
for all device channels. In the
"Off" setting, the device
cannot be reset to the factory
setting. 

Transmission mode

Single, Double
Basic setting: Double

The transmission of all
measured value telegrams is
repeated to guarantee
increased transmission
security (no unsecured
transmission). It is possible to
switch over to simple
transmission.

Settings, channel

Parameters

Setting options, Basic
setting

Explanations

Manual commissioning

On, Off
Basic setting: On

Blocks manual commissioning
for the device channel. In the
"Off" setting, the device
cannot be reset to the factory
setting.

Transmit voltage

On, Off
Basic setting: On

Transmits the current voltage
value.

Transmit current

On, Off
Basic setting: On

Transmits the current current
value.

5/8

82582003
J:0082582003

14.03.2014

eNet

Radio energy detector, 4-channel, for rail mounting

Содержание FM ES 36804 REG

Страница 1: ...andards which apply for SELV circuits Fire hazard Operation exclusively with the power supplies listed under accessories These instructions are an integral part of the product and must remain with the...

Страница 2: ...ntrolled data transmission The energy sensor determines the current consumption data every 0 2 seconds The data can be transmitted at a configurable transmission of 1 60 minutes In addition data trans...

Страница 3: ...As bus line use e g J Y St Y 2x2x0 8 o Connect the device with bus line figure 2 to the RMD reception module and power supply see instructions of RMD reception module and power supply Connecting load...

Страница 4: ...mmissioning interface Removing an energy sensor from the project o In the commissioning interface of the eNet server delete the energy sensor from the current project refer to the technical documentat...

Страница 5: ...planations Manual commissioning On Off Basic setting On Blocks manual commissioning for all device channels In the Off setting the device cannot be reset to the factory setting Transmission mode Singl...

Страница 6: ...he currently cumulated effective energy The value can be reset to 0 or set to any other value Transmission interval 1 60 min Basic setting 15 min The current consumption data is transmitted at the int...

Страница 7: ...of service Device error Measuring status no fault value is corrupted due to failure no fault Measurement active value is corrupted due to failure The sensor is not supplying valid measured values Mea...

Страница 8: ...V for rail mounting Art No NT 1220 REG VDC Master receiver for rail mounting Art No FM FK 32 REG eNet server Art No ENET SERVER 5 5 Warranty We reserve the right to make technical and formal changes...

Отзывы: