background image

Standard / Universal automatic switch 1.1 m

Figure 6: Heat sources in buildings

Some of the mentioned effects can be compensated for using intelligent filter switches by calib-
rating the received signals with typical motion patterns. Selecting the device and installation loc-
ation should be made so that the detection field is suited for the intended purpose.

Technical information and statements

On the one hand the effective range of motion detector applications is affected by a wide range
of factors – however, specifications in the technical data typically come out very precise. These
specifications generally refer to the normal area of use of the device. For flush-mounted motion
detector we assume the typical interior situation in a functional building with moderate ambient
conditions, at a temperature of about 18 °C, average humidity, used in a hallway with walking
people.

Higher ranges are to be expected for:

lower ambient temperature (note season specific clothing)

more intense movement of persons

reflective surfaces

Lower ranges are to be expected for:

higher ambient temperatures, where people move less and there is more heating, such as
is the case with meeting rooms, classrooms, waiting areas and office environments

significantly cooler ambient temperature, when clothing has a thicker insulating effect

Direction of motion to the motion detector for ("radial detection")

rising terrain that limits the geometry of the detection field.

5

Operation

Slide switch

The slide switch serves for local control and sets the operating mode (function block 1).

Figure 7: Slide switch

ON position: Switching on, e.g. light.

OFF position: Switching off, e.g. light

AUTO position: Automatic operating mode. Detected movements within the detection field trig-
ger a switch-on signal.

5 / 13

32597033

24.07.2019

j0082597033

Содержание 3181 Series

Страница 1: ...ce or its accessories are supplied with batteries in the form of button cells DANGER Batteries can be swallowed This can lead directly to death by suffocation Danger ous substances may cause severe in...

Страница 2: ...tion of this device depends upon the software Detailed information on loadable soft ware and attainable functionality as well as the software itself can be obtained from the manu facturer s product da...

Страница 3: ...ough the passive infrared principle PIR The device generally reacts to heat radiation changes within its detection field This is achieved with the help of the so called PIR sensors which are highly se...

Страница 4: ...the concentration of the scan and therefore the response be haviour Sensor sensitivity the sensor sensitivity can be adjusted according to application and en vironment Low heat contrasts outdoors may...

Страница 5: ...perature of about 18 C average humidity used in a hallway with walking people Higher ranges are to be expected for lower ambient temperature note season specific clothing more intense movement of pers...

Страница 6: ...ter dependent or IR reception only for Universal version RD Red Programming mode is active 6 IR remote control Only for Universal version Function buttons IR remote control Button Function Detection o...

Страница 7: ...s re set Switch on e g light Press the button Switch off e g light Press the button Set automatic mode Press the button Manually changing settings with IR remote control If enabled individual settings...

Страница 8: ...The size of the detection field depends on the direction of motion and the adjusted sensitivity As the distance to the detector increases the detection density and sensitivity decrease 4 High sensiti...

Страница 9: ...terference sources in the detection area Interference sources e g heaters vent ilation air conditioners and cooling light bulbs can lead to unwanted detections Limiting the detection field The detecti...

Страница 10: ...igure 14 Range with radial direction of motion Mounting the panel Figure 15 Dismounting of slide switch Figure 16 Dismounting of design cover Figure 17 Mounting cover ranges LS CD and A ranges Ranges...

Страница 11: ...e measurement Universal version compare the temperat ure measurement Testing the detection field In the case of main units and extensions check the detection fields of the devices individually Precond...

Страница 12: ...vironmentally friendly manner Do not throw batteries into household waste Consult your local authorities about environmentally friendly disposal According to statutory provisions the end consumer is o...

Страница 13: ...o 2073U IR remote control Art no KNX PM FB IR 11 Warranty The warranty is provided in accordance with statutory requirements via the specialist trade ALBRECHT JUNG GMBH CO KG Volmestra e 1 58579 Schal...

Отзывы: