Standard / Universal automatic switch 1.1 m
■
Remove the cover from the slide switch (5) (Figure 15).
■
Use a screwdriver to carefully remove the design cover (Figure 16).
■
Mount the cover for the left or right side of the device (3) (Figure 17).
Series A:
■
Mount the cover from the front on the left or right side of the device (Figure 17).
Fitting the device
Prerequisite: Bus coupler (1) is mounted in an appliance box and connected.
■
Install the motion detector (3) with frame (2) onto the bus coupler (1) in the correct orient-
ation.
7.2 Commissioning
Load physical address and application program
■
Carefully remove the cover from the slide switch.
■
Press the programming button.
The red LED in the lens lights up.
■
Assign physical address.
The red LED goes out.
■
Write the physical address on the device label.
■
Load the application program into the device.
In case of active temperature measurement ("Universal" version) compare the temperat-
ure measurement.
Testing the detection field
In the case of main units and extensions, check the detection fields of the devices individually.
Precondition: The device is installed and connected. The physical address is loaded.
■
Activate walking test:
Activate the parameter "Walking test after ETS programming" and download the applica-
tion software.
The device now operates brightness-independently. The PIR sensors are active accord-
ing to their programmed sensitivity.
■
Pace off the detection field, paying attention to reliable detection and interference
sources.
Any motions detected are displayed by the blue LED.
■
Limit the detection field as required. Adjust sensitivity with adjuster Sens. or IR remote
control, or change the programming.
■
Deactivate the parameter "Walking test after ETS programming" and download the applic-
ation software.
Only for "Universal" version:
If enabled, the walking test function can be activated with the button Test of the IR remote
control.