2 Device description
Counters
Counter inputs
Any of the digital signals can be used as input signals for the counters.
v
Chapter 2.4 “Digital signals (event traces)”
Example:
- binary inputs
- logic channels
- alarms
- memory alarms
- Modbus flag (signal via interface)
Counter
frequency
30Hz max.
Evaluation
The count pulses can be evaluated (weighted). A down counter can be
implemented by entering a negative weighting (e.g. weighting factor -1).
Each count change can be documented with an entry in the event list. The
new count is attached to the message.
Integrators
Integrator
inputs
Analog inputs 1 — 3 or 1 — 6 and math channels 1 — 6
Integrator
time base
sec, min, hr and day
Evaluation
You can also enter a weighting for the integrators.
Weighting
example
- measurement of flow volume
- input signal of 0 — 20mA (corresponds to 0 — 500 liters/sec)
- time base 1sec
- weighting 0.001
Result: display of the integration value (volume) in m³.
Minimum size
of the input
signal
Entering a threshold value (amount of the threshold value) has the effect that
integration takes place only when the value has been exceeded. No
integration will occur on falling below this value. The advantage of integration
with a threshold value larger than 0 is that possible noise from a transducer
can be suppressed in this way.
H
If there is an overrange or underrange on an integrator input, then
integration is stopped (the latest valid value is retained), and will
only continue when the input signal is correct again.
Содержание LOGOSCREEN 550 cf
Страница 1: ...Paperless Recorder B 70 6510 0 Operating Manual 03 08 00467986 cf...
Страница 2: ......
Страница 30: ...2 Device description 30...
Страница 112: ...6 Rights 112...
Страница 120: ...9 Installation 120...
Страница 126: ...11 T V Report on Data Manipulation Security 126...
Страница 127: ...127 11 T V Report on Data Manipulation Security...
Страница 128: ...11 T V Report on Data Manipulation Security 128...
Страница 136: ...12 Index 136...
Страница 137: ......