35
9 Configuration
Error behavior
Inaktiv
value: If the
function
parameter of digital output 1 is configured as a
switching output
value, a
process value error sets the
switching output
to
inactive
.
Frozen
value: If the
function
parameter of digital output von 1 is configured as a
switching output
val-
ue, a process value does not have any influence on the configuration of the
switching output
value.
Input/output 1 > digital output 1 > pulse output
Input/output 2
Input/output 2 > analog output 2
Switch-off delay
Input range:
0.000
Input value in s.
0.000 to 100.0
Error behavior
Inactive, active,
frozen
Inactive
Behavior of the output signal in case of a
malfunction
Parameter
Value
Default setting
Description
?
Parameter
Value
Default setting
Description
Output signal
type
p-switching, n-
switching, push-
pull
Push-pull
Parameter function.
Parameter
I/O Pin 1
must be configured as
a
digital output
.
Parameter
function
of digital output 1 must
be configured as a
pulse output
value.
Pulses per unit
Input range:
Output value at
nominal width
Output value in pulses per volume unit (sys-
tem unit of the
volume
parameter).
1 to 100000
Parameter
Value
Default setting
Description
I/O Pin 2
Analog, digital
output, digital in-
put
Digital output
Parameter function.
Parameter
Value
Default setting
Description
Function
Inactive, current
output, voltage
output
Current output
Parameter function.
Parameter
I/O Pin 2
must be configured as
an
analog output
value.
Output signal
Flow, tempera-
ture, pressure
Flow
Parameter output signal.
Scaling start
Input range:
0.000
Process value for the current output (4 mA)
or the voltage output (0 V).
-99999 to 99999
Scaling end
Input range:
Max
device mea-
suring range
Process value for the current output (20 mA)
or the voltage output (10 V).
-99999 to 99999
Error behavior
Low, high, frozen,
substitute value
Low
Output signal in the event of a malfunction
Low: 3.4 mA or 0 V
High: 22 mA or 11 V
Frozen: Last valid value
Replacement value: Input value for the pa-
rameter
replacement value
Содержание flowTRANS US W02