background image

8 Operation

28

Status bar

Process value display 1, Process value display 2

Totalizer, totalizer transmission

Only appears when the totalizer function is active.

Batch

Only appears when the batch function is active.

Process value (5-digit)

If the process value exceeds the 5-digit display range, the number of decimal places for the process val-
ue is reduced.

Pos. Symbol, display

Description

1

ALARM

Shows a device error or a warning.

BATCH

Shows an active batch operation.

SIM

Shows an input that is in simulation mode.

(1)

Pos. Symbol, display

Description

1

Shows negative count mode of the totalizer.

Shows positive count mode of the totalizer.

Shows balanced count mode of the totalizer.

Pos. Symbol, display

Description

1

Shows the fill volume.

Shows the remaining volume.

Pos. Symbol, display

Description

2

12345

Shows the positive process value.

-12345

Shows the negative process value.

∑ -

∑ +

∑ +/-

Содержание flowTRANS US W02

Страница 1: ...40605100T97Z101K000 V1 01 EN 00769022 2022 06 29 JUMO flowTRANS US W02 Ultrasonic flow meter For liquids Brief Instructions...

Страница 2: ...Further information and downloads qr 406051 en jumo info...

Страница 3: ...2 Function 9 3 3 Nameplate 10 3 4 Device ID 11 4 Technical data 12 4 1 Electrical data 12 4 2 Inputs 12 4 2 1 Reference conditions 12 4 2 2 Flow 12 4 2 3 Temperature input 13 4 2 4 Pressure input opt...

Страница 4: ...nnection of analog output 24 7 1 4 Connection of digital output 25 7 2 Connecting the device 26 8 Operation 27 8 1 Display elements 27 8 1 1 Startup display 27 8 1 2 Process display 27 8 2 Interfaces...

Страница 5: ...Contents 12 Shutdown 43 12 1 Uninstalling the device 43 12 2 Returning devices 43 12 3 Disposal 43 13 Accessories 44 14 China RoHS 45...

Страница 6: ...droid is a registered trademark of Google LLC 94043 Mountain View US Apple is a registered trademark of Apple Inc Cupertino Calif US Bluetooth and the Bluetooth logo are registered trademarks of Bluet...

Страница 7: ...conductive liquid media The process values can be mapped via the process display and issued to a higher level system via the outputs During operation the admissible data and operating conditions speci...

Страница 8: ...ent of the fire hazard due to the product materials the admissible environmental influences and the voltage supply 2 6 Declarations of conformity Radio Equipment Directive RED JUMO GmbH Co KG hereby s...

Страница 9: ...provide interfaces for dis playing measured values Function principle Front view Rear view 1 Measuring tube 4 Display TFT display 2 Transducer ultrasonic converter 5 O ring seal for the process connec...

Страница 10: ...up number 6 FCC approval 13 Fabrication number 7 Observe device documentation 14 Part no 8 Measuring range 15 Fabrication number as a DMC code 36039 Fulda Germany 2 3 4 5 11 13 7 6 9 12 14 1 15 10 8 R...

Страница 11: ...15 flowmeter pressure sensor 1 to 10 bar rel JUMO 1849B1 xml 0x184A3_ DN15 flowmeter pressure sensor 1 to 16 bar rel JUMO 184A31 xml Device ID Device version IODD 0x18503_ DN20 flowmeter JUMO 185031 x...

Страница 12: ...dium pressure 1 to 4 bar Measuring tube Horizontal installation compliance with the required inlet and outlet sections Measuring range max DN 15 with Low flow calibration 60 l min DN 15 80 l min DN 20...

Страница 13: ...ogic input external voltage aupply Function Reset totalizer start stop batch measured value suppression Switching voltage VDI DC 30 V VDI 60 V Protection Against polarity and voltage peaks Internal re...

Страница 14: ...ce error Limit value monitoring function Input signals Flow temperature or pressure optional Configuration Hysteresis NO contact NC contact window NO contact NC contact switch on and switch off delay...

Страница 15: ...Transfer of configuration data and device information System requirements iOS device iPhone 7 or later recommended with iOS 13 Android device Android 8 0 or later Communication Via end device with IO...

Страница 16: ...ial requirements Vibration resistance DIN EN 60068 2 6 DIN EN 60068 2 27 Vibration resistance 5 g at 10 to 2000 Hz Shock resistance 20 g over 11 ms Pressure Equipment Directive 2014 68 EU Group 1 flui...

Страница 17: ...0 50 100 150 200 250 0 5 10 15 20 25 30 40 45 50 X Y mbar 35 DN 15 DN 25 DN 20 DN 15 low DN 32 Medium type Conductive or non conductive liquids Viscosity 100 mPas Foreign matter content Solids 5 vol...

Страница 18: ...hnical data 18 4 9 Dimensions Nominal width Di mm P A mm B mm C mm L mm DN 15 16 5 G 1 120 80 43 5 160 DN 20 21 5 G 1 1 4 46 165 DN 25 27 G 1 1 2 49 175 DN 32 34 G 2 52 5 185 L A B C Di P flowTRANS US...

Страница 19: ...e device in a dry and dust free environment Observe the device storage temperature range 5 4 Packaging and transport If the device is not protected properly against external influences it may become d...

Страница 20: ...ons Installation position To calm the flow in the pipeline the specified inlet and outlet sec tions are required at the very least For increased accuracy the inlet and outlet sections can be made long...

Страница 21: ...and two union nuts 2 Select the correct set for the nominal width and pipe material in question For the table of dimensions for the mounting sets please see Data sheet Nominal width Insertion length...

Страница 22: ...s of the mounting set Ensure that the O rings 2 be tween the process connections 1 and union ends 3 are cor rectly positioned 3 Manually screw union nuts on both ends of the pipe to the pro cess conne...

Страница 23: ...he process Do not lay the cable near high voltage or high frequency cables if you cannot avoid doing so main tain a minimum gap of 30 cm 7 1 1 Pin assignment of the M12 connector Connection Device Con...

Страница 24: ...utput I O Pin 1 and or I O Pin 2 can be configured as analog output The connection examples for I O Pin 2 also apply to I O Pin 1 Current output 4 to 20 mA Voltage output 0 to 10 V Device Connecting c...

Страница 25: ...ect an unused current output to GND Leave an unused voltage output open The connection examples for I O Pin 1 also apply to I O Pin 2 Digital output push pull example 1 Digital output push pull exampl...

Страница 26: ...onto the M12 plug connection on the de vice If using the connecting cable provided by the manufacturer tighten the union nut using an SW13 open end wrench Maximum tightening torque 0 4 Nm 3 Connect t...

Страница 27: ...flowTRANS US W02 TAG 01 01 Main SW 439 02 01 Main HW 464 01 01 BT SW I O HW 01 01 JUMO flowTRANS US W02 TAG 01 01 Main SW 439 02 01 Main HW 464 01 01 BT SW I O HW 01 01 1 5 2 3 4 Orientation 0 180 Ori...

Страница 28: ...val ue is reduced Pos Symbol display Description 1 ALARM Shows a device error or a warning BATCH Shows an active batch operation SIM Shows an input that is in simulation mode 1 Pos Symbol display Des...

Страница 29: ...gured system unit of the process value Pos Symbol display Description 1 Interface connection Bluetooth Status Inactive Interface connection Bluetooth Flashing status Wait for connection to establish P...

Страница 30: ...ion Digital output Function Switching output pulse output Status Inactive switching output Configuration Digital output Function Switching output Status Active Pos Symbol display Description 3 Configu...

Страница 31: ...he manufacturer s websites or alternatively using the QR code 8 2 2 IO Link IO Link enables configuration and parameter setting for the device using an end device Process data configuration data and d...

Страница 32: ...ue 2 No signal flow temperature pressure sound velocity signal strength fill vol ume residual vol ume totalizer 1 volume totalizer 1 volume carry over totalizer 2 volume totalizer 2 volume carry over...

Страница 33: ...tion text input with max 32 characters possible Process data for mat Floating point whole number Floating point IO Link output format of process data Activate event Inactive Process Data PD invalid De...

Страница 34: ...error device error Limit value switch Parameter function Parameter I O Pin 1 must be configured as a digital output Parameter function of digital output 1 must be configured as a switching output val...

Страница 35: ...rameter function of digital output 1 must be configured as a pulse output value Pulses per unit Input range Output value at nominal width Output value in pulses per volume unit sys tem unit of the vol...

Страница 36: ...tput value Inversion On Off Off Inverts the output signal Output signal type p switching n switching push pull Push pull Parameter function Limit value moni toring function Inactive hystere sis functi...

Страница 37: ...change in measured value at the output Response time t90 with default setting 2 s Low flow limit val ue Input range 0 050 Input value in of max measuring range of nominal width DN of the device No pro...

Страница 38: ...zero point adjustment Parameter Value Default setting Description Filter time con stant Input range 1 000 Optimization of measured value updating 0 000 to 25 00 The larger the value of the filter tim...

Страница 39: ...put range 0 000 Input value for the simulation 99999 to 99999 Parameter Value Default setting Description Simulation On Off Off Parameter function Value Input range 0 000 Input value for the simulatio...

Страница 40: ...faulty Contact the manufacturer The measuring range was fallen below Operate the device within the device specifications The measuring range was exceeded Operate the device within the device specific...

Страница 41: ...age supply to the device Overload at C Q or DO The switching outputs are overloaded Check the connection and load of the switching outputs Error analog output The burden at the analog output is too hi...

Страница 42: ...stall the device Installing the device Page 22 11 3 Decontaminating the device Requirements Uninstall the device Uninstalling the device Page 43 Wear suitable protective equipment Have a suitable clea...

Страница 43: ...42 Clean the parts that come into contact with the medium Cleaning parts that come into contact with the medium and replacing O rings Page 42 Decontaminate the device Decontaminating the device Page 4...

Страница 44: ...t welding DN 15 00750878 PP butt welding DN 20 00750881 PP butt welding DN 25 00750884 PP butt welding DN 32 00750887 Stainless steel DN 15 with PP nut 00750923 Stainless steel DN 20 with PP nut 00750...

Страница 45: ...mation SJ T 11364 This table is prepared in accordance with the provisions SJ T 11364 GB T 26572 Indicate the hazardous substances in all homogeneous materials for the part are below the limit of the...

Страница 46: ...14 China RoHS 46...

Страница 47: ......

Страница 48: ...oy Road East Syracuse NY 13057 USA Delivery address Mackenrodtstra e 14 36039 Fulda Germany Phone Fax Email Internet 44 1279 63 55 33 44 1279 62 50 29 sales jumo co uk www jumo co uk Phone Fax Email I...