13 Controller
94
13.6 Sample configurations
13.6.1 Simple limit monitoring
Configuration
Limit monitoring
Limit value 1
Signal source:
Main value
Switching function:
Alarm function
(AF8)
Switching point :
6.50 pH
Hysteresis:
0.50 pH
Limit value 2
Signal source:
Main value
Switching function:
Alarm function
(AF7)
Switching point :
8.50 pH
Hysteresis:
0.50 pH
Configuration of binary output, e.g. relay)
Binary outputs
Binary output 1
Signal source:
Limit monitoring 1
At calibration:
Standard operation
Error:
Inactive
HOLD mode:
Frozen
Turn-on delay:
0 seconds
Turn-off delay:
0 seconds
Wiper time:
0 seconds
Manual mode:
No simulation
Binary output 2
Signal source:
Limit monitoring 2
At calibration:
Standard operation
Error:
Inactive
HOLD mode:
Frozen
Turn-on delay:
0 seconds
Turn-off delay:
0 seconds
Wiper time:
0 seconds
Manual mode:
No simulation