7 Installation
18
Connection
✱
Unscrew the housing cover
➩
"Unscrewing the bezel ring or housing cover", page 41.
✱
Insert the cable through the cable gland.
✱
Make the connection according to the connection diagram.
✱
Close the housing cover.
Connection
Terminals
Screw terminals
Assignment
Supply
11.5 — 36 V DC
11.5 — 30 V DC for
intrinsically safe version
1 L+
2 L-
1 L+
2 L-
Output
4 — 20 mA 2-wire
proportional current 4 to 20 mA in supply
1 L+
2 L-
1 L+
2 L-
Test connection for current output
internal resistance of ammeter
≤
10
Ω
TEST +
TEST -
Test connection for HART
®
burden must be present!
TEST +
HART
®
Potential equalization
(with intrinsically safe circuit)
Shield
8
1
+
+
2
-
-
HART
TEST
-
+
Supply
voltage
11.5—36 VDC
Burden
1
1
Burden
≤
(U
B
- 11.5 V) / 0.022 A
Burden with HART
®
min. 250
Ω
, max. 1100
Ω
All manuals and user guides at all-guides.com
Содержание dTRANS p02
Страница 2: ...All manuals and user guides at all guides com...
Страница 5: ...All manuals and user guides at all guides com...
Страница 47: ...45 12 Maintenance All manuals and user guides at all guides com...
Страница 48: ...46 13 Appendix 13 1 EC Type Examination Certificate All manuals and user guides at all guides com...
Страница 50: ...13 Appendix 48 All manuals and user guides at all guides com...
Страница 52: ...13 Appendix 50 All manuals and user guides at all guides com...
Страница 54: ...13 Appendix 52 13 2 Supplement to ECType Examination Certificate All manuals and user guides at all guides com...
Страница 56: ...13 Appendix 54 All manuals and user guides at all guides com a l l g u i d e s c o m...
Страница 58: ...13 Appendix 56 13 3 EU Declaration of Conformity ATEX All manuals and user guides at all guides com...
Страница 61: ...All manuals and user guides at all guides com a l l g u i d e s c o m...
Страница 62: ...All manuals and user guides at all guides com...
Страница 63: ...All manuals and user guides at all guides com...