
4 Commissioning the instrument
15
Lead compensation resistance
This value is used to compensate the resistance of the probe lead and is de-
pendent on the lead length.
For best temperature measurement results, the resistance value of the
probe lead has to be entered here (with short-circuited probe).
0.0
... 99.9 in
Ω
Unit
for the process value displayed
°C
or °F
no (= no unit)
Filter time constant
for adapting the digital input filter.
At a signal step, 63% of the changes are registered after the filter time con-
stant has elapsed.
Values between 0.1 and 0.7 are interpreted as 0.8 (sampling time).
If the filter time constant is long:
- high damping of interference signals
- slow reaction of the process value display to process value changes.
0.1 ...
0.8
... 99.9s
Parameter Meaning
Value range
from...
factory-set
...to
A
If the total resistance at the measurement input (sensor resi
selected value for OF.r) exceeds 320
Ω
with Pt100 and 3200
Ω
with
Pt1000/KTY2x-6, a measurement error will occur !
A
Only the process value at the measurement input will be
correspondingly converted when changing over to °F.
All other variables will retain their values.
H
Return to the first parameter AL of the parameter level with
> 3 seconds.
Содержание DI ECO
Страница 22: ......
Страница 24: ...Digital Indicator B 70 1540 0 B 95 1540 0 Operating Instructions 10 04...
Страница 25: ...Overview of operation...
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......