4 Commissioning the instrument
12
Indicator parameters
Parameter Meaning
Value range
from...
factory-set
...to
Alarm value (limit for relay and LED)
A measured value is considered to be an alarm if
- present value is larger than alarm value
+ ½ hysteresis
and
- has been continuously present for longer than configured under the alarm
suppression time
.
An alarm is reset if
- present value is smaller than the alarm value - ½ hysteresis.
...
0
…
Hysteresis
It is used to determine an alarm.
The hysteresis lies symmetrically about the limit value
.
0.4 ...
1.0
... 99.9°C/°F
Low alarm limit
, together with
, is used to limit the value range for the alarm
value .
-350 ...
-200
... 999°C/°F
High alarm limit
, together with
, is used to limit the value range for the alarm
value .
-350 ...
500
... 999°C/°F