5 Configuration
90
5.15
Wtrans gateway
Settings for using the JUMO Wtrans transmitters are made here (available as of system version 5).
General
Wtrans transmitter
These settings are required for each transmitter selected in the Wtrans hardware configuration (Wtrans
hardware assistant in the Setup program).
NOTE!
Wtrans B (707060) with thermocouple: With system version 5, only types J, K, and B are supported. With
system version 6, all types except MoRe5-MoRe41 and W3Re-W26Re are supported.
Parameter
Selection/data input
Description
Radio frequency
Wtrans radio frequency (MHz)
868.4
Europe
912.6 to 917.4
America, Australia, Canada and New Zealand
Parameter
Selection/data input
Description
General
Name
Enter text (or use existing text) Transmitter designation
Transmitter ID
0 to 99999
ID of the Wtrans transmitter
The unique ID set on the transmitter side must also
be set here to identify the transmitter.
Radio timeout
2
to 20
Number of radio telegrams not received, which
leads to timeout detection.
The set transmission interval of the transmitter is
transmitted with the radio telegram. When the first
telegram is received, this value is saved in the re-
ceiver and the radio timeout monitoring function is
activated. If no new telegram is received through-
out the entire timeout period, the measured value
is set to "no input value" and the "Radio timeout"
alarm is activated.
Analog processing
Name
(for Wtrans E01;
as of system ver-
sion 6)
Enter text (or use existing text) Designation of measured value
Factor
-99999 to 99999
(1)
Factor for correction of the measured value
Offset
-99999 to 99999
(0)
Offset value for correction of the measured value
Linearization
Select linearization from selec-
tor (customer-specific linear-
ization: formula or grid points)
Linearization for the measured value
Configuration of linearization: Configuration > De-
vice manager > Customer-specific linearization
Содержание 705003
Страница 2: ......
Страница 6: ...Contents...
Страница 20: ...1 Introduction 20...
Страница 25: ...25 2 Mounting 2 3 Dimensions 101 110 5 45 94 5 101 5 17 5...
Страница 26: ...2 Mounting 26...
Страница 68: ...4 Operation 68 The files are available for download in the web browser click on the file...
Страница 94: ...5 Configuration 94...
Страница 98: ...6 Startup 98...
Страница 109: ...109 7 Annex 7 5 China RoHS...
Страница 110: ...7 Annex 110...
Страница 111: ......