79
5 Configuration
Tolerance band monitoring
Setting of setpoint values: setpoint specification
Setting of setpoint values: setpoint limits
Parameter
Selection/data input
Description
Alarm type
Inactive
The tolerance band monitoring is not active.
Event
The tolerance band violation is entered as an
event in the event list.
Alarm
The tolerance band violation is entered as an
alarm in the event list and the alarm list.
Alarm at level
High
Alarm at high level (1 = actual value outside the tol-
erance band)
Low
Alarm at low level (0 = actual value within the tol-
erance band)
Event text
Enter text (or use existing text) This text is entered in the relevant list in the event
of a violation of the tolerance band.
Hold when toler-
ance band is ex-
ceeded
If the tolerance band is violated, the program can
be stopped until the condition is over.
Yes
The program is stopped.
No
The program is not stopped.
Parameter
Selection/data input
Description
Setpoint value 01
to Setpoint value
30
Specification of whether a change made to the set-
point value should take the form of a step or a
ramp.
Setpoint step
Setpoint value change as step
Setpoint ramp
Setpoint value change as ramp
End value for setp. ramp 1 to
End value for setp. ramp 10
The relevant setpoint value acts as the end value
for the ramp function of the setpoint value (1 to 10)
which is selected here.
If there is no end value specified in a program sec-
tion, then the program generator works in accor-
dance with its configuration (setpoint step or
setpoint ramp).
Parameter
Selection/data input
Description
Decimal places
Auto
The number of decimal places is selected auto-
matically.
XXXXXp
No decimal place
XXXXpX
One decimal place
XXXpXX
Two decimal places
XXpXXX
Three decimal places
XpXXXX
Four decimal places
Lower tolerance band limit (tol. band lower limit)
Minimum
-99999
to 99999
Admissible minimum value for the lower tolerance
band limit
Maximum
-99999 to
99999
Admissible maximum value for the lower tolerance
band limit
Содержание 705003
Страница 2: ......
Страница 6: ...Contents...
Страница 20: ...1 Introduction 20...
Страница 25: ...25 2 Mounting 2 3 Dimensions 101 110 5 45 94 5 101 5 17 5...
Страница 26: ...2 Mounting 26...
Страница 68: ...4 Operation 68 The files are available for download in the web browser click on the file...
Страница 94: ...5 Configuration 94...
Страница 98: ...6 Startup 98...
Страница 109: ...109 7 Annex 7 5 China RoHS...
Страница 110: ...7 Annex 110...
Страница 111: ......