JUMO 705003 Скачать руководство пользователя страница 1

70500300T90Z001K000

V5.00/EN/00748411/2022-06-07

JUMO variTRON 300

Automation System

Central Processing Unit 705003

Operating Manual

Содержание 705003

Страница 1: ...70500300T90Z001K000 V5 00 EN 00748411 2022 06 07 JUMO variTRON 300 Automation System Central Processing Unit 705003 Operating Manual...

Страница 2: ......

Страница 3: ...le overview 14 1 7 1 Central processing unit 14 1 7 2 Modules 15 1 8 Available technical documentation 18 1 8 1 Central processing unit 18 1 8 2 Input output modules 18 1 8 3 Special modules 19 1 8 4...

Страница 4: ...LC application 48 4 3 9 PLC parameter definition 49 4 3 10 Languages 50 4 3 11 Data transfer 52 4 3 12 Messages 55 4 3 13 Connections 56 4 4 JUMO Web Cockpit 58 4 4 1 Device information 61 4 4 2 Event...

Страница 5: ...ateway 90 5 16 Node RED 91 5 17 Batches 92 6 Startup 95 7 Annex 99 7 1 Technical data 99 7 1 1 Interfaces 99 7 1 2 Display 101 7 1 3 Electrical data 101 7 1 4 Housing and environmental conditions 102...

Страница 6: ...Contents...

Страница 7: ...This symbol indicates that components could be destroyed by electrostatic discharge ESD Electro Static Discharge if the respective cautionary measures are not taken Only use the ESD packages intended...

Страница 8: ...nal injury or material damage To avoid danger only use the device For the intended use When in good order and condition When taking the technical documentation provided into account Risks resulting fr...

Страница 9: ...accompanying letter for repair supplementary sheet for product returns can be downloaded online from the manufacturer s website http productreturn jumo info Protection against electrostatic discharge...

Страница 10: ...t and disposal must be observed Disposing of the device DISPOSAL Devices and or replaced parts including batteries should not be placed in the refuse bin at the end of their service life but must be d...

Страница 11: ...ly identifies an article in the catalog It is important for communication between the customer and the sales department Fabrication number F Nr The fabrication number indicates among other things the...

Страница 12: ...ssing unit can be extended with various functions through extra codes For perfor mance reasons it may not be possible to use all functions extra codes simultaneously depending on the application As a...

Страница 13: ...nna cable length 3 m impedance 50 ohm with preconfigured screw type connec tion Tmax 85 C 00482646 Antenna cable length 5 m impedance 50 ohm with preconfigured screw type connec tion Tmax 85 C 0049006...

Страница 14: ...a web browser Visualizations have to be implemented with CODESYS resources see order details A convenient setup program is used for configuration JUMO standard functions for CODESYS are pro vided in l...

Страница 15: ...measuring probes Wtrans T Wtrans B Wtrans p A maximum of 32 transmitters can be operated on the central processing unit During startup the display of the RSSI value Received Signal Strength Indicator...

Страница 16: ...rail side system bus input and output Is used exclusively for system bus expansion via RJ45 sockets on the front 2 x Bus Out Router module 3 port as of system version 3 705042 Use as first module on a...

Страница 17: ...17 1 Introduction Power supply unit 705090 10 33 705090 AC 100 to 240 V wide range input Output DC 24 V 10 A Module designation Data sheet Features...

Страница 18: ...4 channel Data sheet 70501500T10 X Operating manual 70501500T90 B 705015 0 X Installation instructions 70501500T94 B 705015 4 X X Analog input module 4 channel Data sheet 70502000T10 X Operating manu...

Страница 19: ...70906x as of system version 3 Operating manual integration in the automation sys tem 70500153T90 X Product Document No Printed PDF file Router module 2 port as of system version 3 Data sheet 70504100T...

Страница 20: ...1 Introduction 20...

Страница 21: ...ical data can be found in data sheet 705070 Climatic conditions The ambient temperature and the relative humidity at the mounting site must correspond to the technical data Aggressive gases and vapors...

Страница 22: ...must always be installed on the left side at the start of the DIN rail A central processing unit or A router module 705042 or 705043 These connect the input output modules to the voltage supply and th...

Страница 23: ...3 Process 1 Mount the central processing unit A on the DIN rail from above A1 2 Pivot the central processing unit A downwards until it snaps into place A2 NOTE If necessary activate the terminating re...

Страница 24: ...equired use a screwdriver to release the wired terminal B of the central processing unit A and pull off toward the front B1 3 Insert a suitable screwdriver C into the unlocking slot of the central pro...

Страница 25: ...25 2 Mounting 2 3 Dimensions 101 110 5 45 94 5 101 5 17 5...

Страница 26: ...2 Mounting 26...

Страница 27: ...he control cabinet In doing so ensure that the cables are as short as pos sible Ensure that the potential equalization is correct Electrical safety Isolate power supply units from the voltage supply o...

Страница 28: ...lt the insulation of the cable may be damaged The cable must be heat resistant up to at least 80 C NOTE Only copper conductors are allowed to be connected to the terminals 3 3 1 Display operating and...

Страница 29: ...resistors RS485 inside the housing 1 6 1 2 3 4 5 7 8 9 Connection Designa tion Num ber Connection element Assignment Antenna optional 1 SMA socket Ethernet LAN1 LAN2 6 5 1 TX 2 TX 3 RX 6 RX Transmiss...

Страница 30: ...and 2 must be closed The switches are located inside the housing and are accessible through the ventilation slots 1 NOTE To ensure fault free operation terminating resistors are required at the beginn...

Страница 31: ...DHCP is active User log on Please use the following details to log on for startup purposes User name Master Password 9200 The password should be changed by the end of startup at the latest The passwor...

Страница 32: ...ch between displaying the system status and the system bus status 8 Up key in menu increase value select previous menu item parameter or value in basic status switch between displaying the system stat...

Страница 33: ...System status chapter 4 4 1 Device information Page 61 Configuration Sub menu 1 Sub menu 2 Sub menu 3 Logon log in User to be selected password to be entered Logoff log out Sub menu 1 Sub menu 2 Sub m...

Страница 34: ...lay Total root volume memory dis play Product group display Recorder service ID display Certification number inspection number display Fabrication number production number display Hardware versions de...

Страница 35: ...firm 5 Enter the subsequent digits of the password one after the other 6 Once you have entered the last digit press the Menu OK key again Sub menu 1 Sub menu 2 Sub menu 3 Device manager Activate debug...

Страница 36: ...been activated CAUTION Reset to default settings All data will be deleted All settings will be reset to the default settings JUMO including the user admin istration settings user Master password 9200...

Страница 37: ...tup program must also be taken into account Functions provided in the left hand bar also known as the application bar Projects Create new project open existing project Connections Configure and manage...

Страница 38: ...pplication Determine the start parameters for the CODESYS PLC programming system start the PLC configuration process CODESYS PLC parameter definition function is provided if the CPVE is installed Dete...

Страница 39: ...able Version of the setup project Device version non editable Version of the device software Project name button Opens a window for entering a designation for the project in several languag es Descrip...

Страница 40: ...on and magnifying glass icons Since the variTRON 300 CPU does not have any lateral connections for power supply and system bus a router module is required primary router module 1 port to connect furth...

Страница 41: ...itable Designation button Opens a window for entering a designation for the system component in sev eral languages Module label Tag name for the system component editable can no longer be changed once...

Страница 42: ...device address The router module and the components of its HC group optional modules need not be available All input output modules connected to it are also optional modules Router modules connected...

Страница 43: ...rrelevant the addresses are not compared The router module is then a mandatory module The alias device address is freely selectable but must be unique within the system All input output modules connec...

Страница 44: ...r and under each other self expanding grid scroll function horizontal and vertical The view can be enlarged or reduced using the zoom function and magnifying glass icons The position of a transmitter...

Страница 45: ...nables certain settings to be configured Product group number non editable Module label Tag name for the system component editable can no longer be changed once the hardware configuration has been app...

Страница 46: ...s for absolute and relative temperature values for the PLC application con figuration of program generators analog and digital variables as of system version 5 PLC parameters Display of the configurat...

Страница 47: ...he communication within the system For this reason these parameters are only permitted to be modified by a service engineer from the device manufacturer or by someone acting on their instructions The...

Страница 48: ...ewly initialize the CODESYS plug in e g after uninstalling and reinstalling CODE SYS Programming system Select the CODESYS version drop down menu Most recently edited with programming system display o...

Страница 49: ...ly available if the CPV Editor has been installed NOTE The CPV Editor is used to create customer specific configuration and process data The CPV Editor requires specific knowledge and is intended for...

Страница 50: ...ge settings Parameters functions Use application language Use the language of the setup program as the project language Project language button not active if the application language is being used Sel...

Страница 51: ...n the language Standard exports all default texts of the so called development language Select the target language if necessary add your desired target language to the list of project languages before...

Страница 52: ...logging on to the device Version cannot be edited here Device software version of the connected device Connect Establish a connection to the device Disconnect Break the connection Load from device Lo...

Страница 53: ...PLC param eters is not modified in the setup project However known parameters in the project structure are applied from the device structure Only modify structure only for PLC Parameter The structure...

Страница 54: ...own parameters Programs Yes red Only visible values of known parameters System status UI Yes red Only visible values of known parameters Real time processing as of system version 6 Yes red Only visibl...

Страница 55: ...55 4 Operation 4 3 12 Messages Display and act on project messages Project messages that require user action acknowledge message perform further actions if necessary are displayed here...

Страница 56: ...for the connection using the setup program Use secure connection TLS SSL FALSE gray no TRUE red yes default setting This setting affects the port numbers for the connection see above The following por...

Страница 57: ...ameter that has just been changed is shown at the bottom of this window Clicking the Back button circular arrow after the line containing the changed parameter above discards your data entry Both area...

Страница 58: ...eb browser for example 10 178 59 209 8090 You will need your user name and password to log on to the device Once you have successfully logged on the homepage of the web application is shown Homepage D...

Страница 59: ...ce System bus users firmware EtherCAT system bus Display information on the master and slaves modules perform actions Only for variTRON 300 Wtrans gateway status of transmitters User management Create...

Страница 60: ...sses the function Service Wtrans gateway directly User button Designation Description Master The user name of the logged on user is displayed here Info Displays information about the web application S...

Страница 61: ...he retain area1 are de leted see CODESYS documentation on origin full reset of PLC An event message is issued origin reset RESET COLD The PLC performs a cold start which means that the retain area1 is...

Страница 62: ...rval 4 4 2 Events Event messages are extracted from the device and listed in chronological order here The information shown can be filtered by message type alarm audit trail malfunction event It is al...

Страница 63: ...influence the transfer of data via the system bus Sub optimal settings here will disrupt or even interrupt the communication within the system For this reason these parameters are only permitted to b...

Страница 64: ...igured and activated available as of system ver sion 6 Cloud gateway The connection to the JUMO Cloud available as of system version 4 is configured here Wtrans gateway only for variTRON 300 Settings...

Страница 65: ...s activated in the system bus state Operational the system bus goes into the state Initialization This interrupts the cyclic transmission of values Use this function for servicing purposes only Wtrans...

Страница 66: ...x Configuration Write Write configuration several single rights X FirmwareUpdate Perform a firmware update X SystemStateControl Change the system status X BusControl Change the system bus status Stop...

Страница 67: ...ipt in such a way that they are available again for transfer to the device after a factory reset Firmware The device s firmware is updated here For this purpose switch the device to the status Stop Th...

Страница 68: ...4 Operation 68 The files are available for download in the web browser click on the file...

Страница 69: ...configuration has been changed on the device this change will not take effect until you confirm the query Save settings using the Menu OK key In the web application selecting Save ensures the device...

Страница 70: ...ails a software update is re quired Possible errors during the boot process Error in the device software Interruption of the voltage supply Parameter Selection data input Description Device name Enter...

Страница 71: ...P address via a DNS server see Configuration Ethernet Maximum round trip time 0 bis 99999 5 Maximum time in seconds between the client s re quest and the server s response for local time server Parame...

Страница 72: ...ue of Y stands for the linearized value e g temperature in C 99999 to 99999 0 max up to 20th order Parameter Selection data input Description Parameter Selection data input Description Name Enter text...

Страница 73: ...ed before the system bus switches to the status Stop Continuationafter system bus error run after s bus err The device can continue automatically as soon as a system bus error that previously occurre...

Страница 74: ...r the network drive Examples Drive1 Drive2 Network path Enter text Network path of the drive Examples Server NetDrive Server NetDrive2 File system SMB CIFS Network file system SMB CIFS is supported up...

Страница 75: ...ate way 0 0 0 0 to 255 255 255 255 IP address of the standard gateway router if the IP address is manually assigned The IP address of the standard gateway may need to be requested from the administrat...

Страница 76: ...e email server Authentication Authentication at logon to email server None No authentication Password Authentication using password Password Enter password Password for authentication Encryption Type...

Страница 77: ...xt or use existing text Designation of program generator Function Inactive The program generator is switched off Program generator The program generator is controlled by a program Fixed setpoint gener...

Страница 78: ...to whether the program pro file had a positive or negative slope at the time of the power failure Start with time The program can be started at a specific time en try of date and time by means of ope...

Страница 79: ...ped Parameter Selection data input Description Setpoint value 01 to Setpoint value 30 Specification of whether a change made to the set point value should take the form of a step or a ramp Setpoint st...

Страница 80: ...Parameter Selection data input Description Lower tolerance value tol min 99999 to 99999 Lower value of the tolerance band Upper tolerance value tol max 99999 to 99999 Upper value of the tolerance band...

Страница 81: ...ific knowledge and is intended for use by the manufacturer only service that is subject to a fee Parameter Selection data input Description Setpoint value 01 unit to Setpoint value 30 unit Unit of the...

Страница 82: ...rogram informa tion Enter text or use existing text Description of the program Pictogram name Select pictogram Pictogram icon for graphical identification mark ing of the program Favorite Programs mar...

Страница 83: ...repetitions of a program section or multiple linked program sections Setpoint value 01 to Setpoint value 30 1000000 to 1000000 The limits depend on the ad missible minimum and maxi mum setpoint value...

Страница 84: ...ration of the device display Screensaver Parameter Selection data input Description Function Activate screen switch off Off The function is inactive On The screen is switched off once the waiting peri...

Страница 85: ...ed In case of configuration with the Web Cockpit a fault message is immediately entered into the event list NOTE The process values are only temporarily stored in the central processing unit to bridge...

Страница 86: ...l binary signal System version 5 Digital PLC outputs binary val ues 001 to 120 or signal from the event list cen tral detector active after each new alarm inactive after acknowledgement As of system v...

Страница 87: ...ange underflow Number of values with measuring range overflow Number of valid value Number of invalid values Post trigger time s 0 to 10 0 Extends event operation after the control signal has been dea...

Страница 88: ...Data export Export of the recorded process data Inactive The function is switched off Active The function is active The data is transferred to the datastore at the set time interval period Datastore...

Страница 89: ...oud server If the JUMO Cloud is not used a different URL can be entered here Individual URL for MQTT as of system ver sion 05 Enter URL URL of the cloud server MQTT protocol If the JUMO Cloud is not u...

Страница 90: ...nsmitter side must also be set here to identify the transmitter Radio timeout 2 to 20 Number of radio telegrams not received which leads to timeout detection The set transmission interval of the trans...

Страница 91: ...lection data input Description Graphical pro gramming tool Node RED Activation of Node RED in the central processing unit Inactive Node RED is not active Active Node RED is active and can be used with...

Страница 92: ...ng process Otherwise there is a risk that the batch documentation will become unusable General information Batch lines For each batch up to 10 lines can be defined for the batch report Parameter Selec...

Страница 93: ...xt specified in the configura tion after the batch has been completed Off FALSE Text changes are retained On TRUE The original text default text is used for the next batch reporting Default text Enter...

Страница 94: ...5 Configuration 94...

Страница 95: ...iTRON 300 CPU does not have any lateral connections for power supply and sys tem bus a router module is required primary router module 1 port to connect further modules In the setup program this route...

Страница 96: ...ogram System bus hardware assistant Change module designation if necessary b Setup program Configuration Real time processing Data recording Modules Groups Group x Assign a meaningful designation for...

Страница 97: ...ed from the setup program the option Start to debug must be activat ed After that the connection with the PLC can be established in the CODESYS programming environment If the CODESYS application is ch...

Страница 98: ...6 Startup 98...

Страница 99: ...Application Communication with PC setup program web browser email server Modbus TCP master slave PROFINET IO device EtherCAT slave OPC UA client BACnet IP server client JUMO system bus via JUMO variT...

Страница 100: ...h a 3 m antenna cable when mounting the antenna directly to the receiver a reduction in the range must be taken into account Required RSSI value for error free transmission 90 with stationary transmit...

Страница 101: ...mm Conductor cross section on terminals 1 and 2 COM Wire or stranded wire without ferrule Min 0 14 mm2 max 1 5 mm2 Stranded wire with ferrule Without plastic collar min 0 25 mm2 max 1 5 mm2 With plas...

Страница 102: ...nge 40 to 70 C Resistance to climatic conditions Relative humidity 90 annual average without condensation cli mate class 3K3 acc to DIN EN 60721 3 3 with extended tempera ture and humidity range Site...

Страница 103: ...the buffer battery The country specific require ments regarding changes to an electrical device must be observed Before replacement the system must be shut down and isolated from the power supply CAU...

Страница 104: ...sly provided in this document 2 Loosen both locking hooks A one after the other using a screwdriver To do this insert the screw driver into the small slot B below the locking hook and turn carefully m...

Страница 105: ...on and ensure that both locking hooks en gage 2 If applicable place the central processing unit back on the top hat rail To do this please follow the instructions on installation previously provided i...

Страница 106: ...s off Single flickering LED flashes briefly 50 ms on 200 ms off Blinking LED flashes 200 ms on 200 ms off Single flash LED flashes once 200 ms on 1000 ms off Double flash LED flashes twice on off on f...

Страница 107: ...odule Start error Incorrect optional board 1 2 3 actual target LED Check optional board and replace load or remove as required replace module if necessary Bus status No connection to central processin...

Страница 108: ...H Co KG will provide the source code and the license texts on a con ventional data carrier at the cost incurred by creating the data carrier This offer is valid for three years after the software is m...

Страница 109: ...109 7 Annex 7 5 China RoHS...

Страница 110: ...7 Annex 110...

Страница 111: ......

Страница 112: ...oy Road East Syracuse NY 13057 USA Delivery address Mackenrodtstra e 14 36039 Fulda Germany Phone Fax Email Internet 44 1279 63 55 33 44 1279 62 50 29 sales jumo co uk www jumo co uk Phone Fax Email I...

Отзывы: