19
Faults
6.
Faults
In order to ensure unit safety and leak
tightness, only approved persons may
open the units and replace parts subject
to water pressure.
At the start of the regeneration a timing
element of around 5 hours is started. If the
regeneration is not completed within this
time an error message is triggered. The
occurrence of a fault in the unit is signalled
by an intermittent buzz.
Deleting the error message:
Disconnect the power pack from
the socket. Plug it back in after
approx. 5 seconds!
Help with faults:
Fault
Cause
Remedy
Fault message
Temporary failure of the
pipe pressure!
–
Delete fault signal.
–
Trigger regeneration manually (see
chapter “Commissioning”).
Late salt refill.
During regeneration the
driving wheel was
manually turned.
The drive turns the driving wheel until the
normal operating position is reached again.
Then the red control lamp goes out and the
softener is again ready for use.
Operating error e.g. in
the hardness setting.
Reset the DIP switch (see chapter “Com-
missioning”).
Renewed fault
signal after
deleting the fault
signal 5 hours
ago!
With bypass facility:
–
Set to bypass!
–
Disconnect the power pack from the
socket! (If installed, disconnect the
power pack of the downstream metering
pump too).
–
Immediately notify the fitter or nearest
customer service.
Without bypass facility:
–
Disconnect the power pack from the
socket! (If installed, disconnect the
power pack of the downstream metering
pump too).
–
Immediately notify the fitter or nearest
customer service (see chapter “Stoppa-
ges”).