JUDO QUICKSOFT-DUO
Installation
4.1.8 Assembling the softener to the
pre-assembled bypass valve
The connection flange of the softener is
covered by a white protective disc. This pro-
tective disc is fastened with four cylinder
head screws M6x25.
–
Loosen all four cylinder head screws
M6x25, but don’t remove them (bayonet
fixture)!
–
Remove the white protective disc.
ATTENTION
Do not grasp into the connection flange
of the device after removing the white
protective disc (danger of violent pres-
sure)!
The section of the profiled flange gasket
must point towards the bypass valve. Failure
to observe this can lead to leaks and water
escaping. This can in turn cause water dam-
age to the house and its installations.
–
Lift up the softener and swivel it through
approx. 30° in an anti-clockwise direction.
–
Position it on the flange of the bypass
valve marked with the cast in letter "G"
(unit flange) so that the screw heads
pass through the bayonet fixing drill
holes.
–
Swivel the softener through approx. 30°
back in a clockwise direction.
–
Tighten the four cylinder head screws
M6x25.
After assembling the softener unscrew the
wall support so far that it rests against the
softener casing and the softener hangs
vertically to the wall.
4.1.9 Wastewater connection and
back-up overflow hose
The hoses for the regeneration wastewater
and the back-up overflow must both be laid
up to the wastewater sewer without any
kinks. Ensure free discharge above the
wastewater channel or floor drain.
The waste water hose with 10 mm of outside
diameters may not be shifted more highly
than the control actuator. The tube length
may amount to maximally 3 m. Securely fix
the loose end of the hose to the pipe or
similar with the adhesive tape supplied.
The back-up overflow hose with a 19 mm
outer diameter must be laid with a constant
fall to the wastewater sewer and free of
kinks.
If the connection for the wastewater sewer is
higher than this, the salt container can be
installed correspondingly higher with the aid
of a wall bracket (see chapter “Accesso-
ries”).
ATTENTION
(see chapter “Safety information and
dangers due to non-compliance”)
The wastewater connection must not be
located above the softener.
An adequately dimensioned wastewater
connection (e.g. floor drain) to DIN 1986
must be available for the wastewater and
the back-up overflow hose.
Select the torque (approx. 4 Nm) so
that the gasket closes and the
softener is not damaged or strained!