57
Modul-AIR Exhaust Air Heat Pump Installation Guide
Power Specification
Modul-AIR Electrical Connections
The Heat Pump power cable is to be connected to a suitably sized isolator which disconnects all poles with
a contact gap of at least 3mm. The isolation switch is not standard with the Modul-AIR supplied. The Isolator
allows for disconnection of the electrical power supply for maintenance and/or repair of the Heat Pump.
The Heat Pump is to be wired to the mains through use of a suitably sized RCBO.
•
Check all connections and the mains voltage is correct before powering On the Heat Pump to prevent
damage to the Heat Pumps electronics.
•
If the power cable is damaged, contact Joule to have it repaired before powering On the Heat Pump.
•
The electrical installation must be carried out by a suitably qualified electrician or under the supervision
of one. All installation work and cabling must comply to local building regulations .
The Heat Pump MUST not be powered on unless the system is filled
with water and at the recommended pressure.
Содержание HHH-AEHP-00001
Страница 11: ...11 Modul AIR Exhaust Air Heat Pump Installation Guide Modul AIR Type Plate Green Comfort Type Plate...
Страница 32: ...32 www jouleuk co uk www joule ie Modul AIR Concrete Block Wall Build up 1 3 4 6 8 5 2 7...
Страница 34: ...34 www jouleuk co uk www joule ie Modul AIR and Green Comfort Concrete Block Wall Build up 1 4 10 5 6 9 2 3 7 8...
Страница 36: ...36 www jouleuk co uk www joule ie Modul AIR Timber Stud Build up 1 4 8 7 2 5 6 3...
Страница 38: ...38 www jouleuk co uk www joule ie Modul AIR and Green Comfort Timber Stud Build up 8 7 6 5 4 3 1 2 10 9...
Страница 71: ...71 Modul AIR Exhaust Air Heat Pump Installation Guide Modul AIR Unit Menu Overview...
Страница 72: ...72 www jouleuk co uk www joule ie...
Страница 115: ...115 Modul AIR Exhaust Air Heat Pump Installation Guide...