49
Modul-AIR Exhaust Air Heat Pump Installation Guide
General Pipework
Sizing, positioning and pre-charge pressure of the heating system
expansion vessel
The Exhaust Air Heat Pump does not have an expansion vessel incorporated. The installer must ensure the
system is protected from the effects of expansion by installing a suitably sized expansion vessel.
The vessel prevents water pressure spikes in the system by absorbing the increased pressure as the
temperature increases.
•
Only use dry nitrogen or air to set the expansion vessel pressure.
•
Inappropriate setting of the expansion vessel pre-charge pressure will lead to malfunction of the
system.
•
The pressure should only be set and/or adjusted by a competent installer.
•
The adjusting of the pressure should be done before the expansion vessel is installed - i.e. the pipe
connection must be open to atmosphere.
The vessel must be sized in accordance with EN 12828. The following system data will assist in sizing a vessel:
1
Vessel pre-charge pressure
*-0.5 bar below working pressure
2
Safety valve set pressure
3 bar, industry standards
3
**The difference in height (H)
0 m, typical install setup
4
Total system volume, in litres
Calculated by the installer
5
System maximum temperature
65°C
6
% Antifreeze glycol in the system
Zero, as it’s an indoor installation
* A pre-charge pressure of 0.5 bar equates to a static head of 5 metres.
** The difference in height (m) is the difference between the position in which the safety valve is installed
and the position of the vessel.
Pre-Charge Pressure 0.5 bar
Pre-Charge Pressure 1.0 bar
Содержание HHH-AEHP-00001
Страница 11: ...11 Modul AIR Exhaust Air Heat Pump Installation Guide Modul AIR Type Plate Green Comfort Type Plate...
Страница 32: ...32 www jouleuk co uk www joule ie Modul AIR Concrete Block Wall Build up 1 3 4 6 8 5 2 7...
Страница 34: ...34 www jouleuk co uk www joule ie Modul AIR and Green Comfort Concrete Block Wall Build up 1 4 10 5 6 9 2 3 7 8...
Страница 36: ...36 www jouleuk co uk www joule ie Modul AIR Timber Stud Build up 1 4 8 7 2 5 6 3...
Страница 38: ...38 www jouleuk co uk www joule ie Modul AIR and Green Comfort Timber Stud Build up 8 7 6 5 4 3 1 2 10 9...
Страница 71: ...71 Modul AIR Exhaust Air Heat Pump Installation Guide Modul AIR Unit Menu Overview...
Страница 72: ...72 www jouleuk co uk www joule ie...
Страница 115: ...115 Modul AIR Exhaust Air Heat Pump Installation Guide...