background image

NOTICE

Accessories  for  woodstoves  for  clearance  reduction  have

been  developed  by  many  manufacturers.  If  not  following

the  methods  of  the  installation  codes,  be  sure  that  any

accessory  you  choose  has  been  tested  by  an  independent

laboratory  and  carries  the  laboratory’s  testing  mark.

Make  sure  to  follow  all  of  the  manufacturer’s

instructions.

Always  contact  your  local  building  inspector  or  fire

officials  about  restriction  and  requirements  in  your  area.

Reminder,  it  is  the  local  officials  who  have  final  authority

in  the  installations  approval.

ALCOVE

The OSLO F500 can be installed in an ALCOVE

situation provided:

      

 See figures 9 and 10.

1.  The stove must be installed with listed double

     wall pipe.

2.  In a PROTECTED alcove installation both side

     walls and rear wall  must be protected per NFPA

     211 or CAN/CSA-B365.  The wall protection

     must be elevated 1” from the floor  and at least 1”

    off the combustible wall to allow  for an air-flow.

3.  The height of the wall protection including the

     bottom air space must be 48”.

4.  The Bottom heatshield is required in all Alcove

     installations.

5.  If a listed (UL/ULC) hearth board is NOT used

     the hearth that is constructed MUST have a

     minimum R value of 1.6 (see Appendix A).

6.  Minimum ceiling height in an unprotected installa

     tion, off the top of the stove is  41”(1040mm) The

     minimum ceiling height off the top of the stove  in

    a protected ceiling  installation is 15”(380mm).

7. ALCOVE floor protection must be: a UL/ULC

or WHI listed hearth pad 

or

 a non combustible

material with a minimum R value of 0.5.

In  Canada,  refer  to  CAN/CSA-B365, 

Installation

Code  for  Solid-Fuel  Burning  Appliances  and

Equipment

,  also  for  acceptable  materials,  proper

sizing and construction guidelines.

Stove Mounted Heatshield:  A stove rear heatshield

has been specifically  designed for the OSLO F500.
In  the  U.S.  and  Canada  the  rear  heatshield  part

number is # 154332.

NO   OTHER   HEAT  SHIELD   MAY   BE   USED.

MOBILE  HOME  INSTALLATIONS

The OSLO F500 has been approved for use in mobile

homes in the U.S. and Canada, provided:

1. The stove is secured to the floor or the mobile

home. Floor mounting kit #750304

2. The stove is provided outside air for combustion.

Outside Air kit  #154335(

see page 16 for more details)

3. The stove must be grounded to the mobile home

frame per NFPA 70.

As  always  consult  with  your  local  building

inspector or fire officials about restrictions and

requirements in your area, prior to installing the

stove.

56.5”  min.

(1435mm)

UNPROTECTED ALCOVE INSTALLATION

*

max.  depth

48”  (1220mm)

14”

355mm

14”

355mm

18”

460mm

* USE OF THE LEFT SIDE LOAD DOOR IS  PROHIBITED

   IN ALCOVE  INSTALLATIONS.

40.5”  min.

1015mm

  max.  depth

  48”  (1220mm)

PROTECTED ALCOVE INSTALLATION

*

* USE OF THE LEFT SIDE LOAD DOOR IS  PROHIBITED

   IN ALCOVE  INSTALLATIONS.

150mm

150mm

12”

300mm

PROTECTION

AND  AIR

SPACE  MUST

COMPLY

WITH  NFPA

211OR

CAN/CSA-B365.

10

FIGURE    9

FIGURE  10

Содержание Oslo F 500

Страница 1: ...instructions for future reference Avis de s curit Une installation non appropri e de ce po le de chauffage risque de provoquer un incendie Assurez votre s curit en respectant les directives d installa...

Страница 2: ...tallations 10 Mobile Home Installations 10 Operation 13 Controls 13 Breaking in your Stove 13 Starting Maintaining 14 Formation of Creosote 14 Maintenance 15 Ash Removal 15 Glass Care 15 General Maint...

Страница 3: ...lways consult your local building inspector or authority having jurisdiction to determine what regulations apply in your area NOTICES BE SURE TO READ THIS ENTIRE MANUAL BEFORE YOU INSTALL OR USE YOUR...

Страница 4: ...h no more than two 90 elbows The maximum horizontal run is 36 and a recommended total length of stove pipe should not exceed 10 feet Always slope horizontal runs upward per foot toward the chimney No...

Страница 5: ...of the chimney 5 CHIMNEY REQUIREMENTS There are two types of chimneys suitable for the OSLO F500 1 A code approved masonry chimney with a flue liner 2 A prefabricated chimney complying with the requir...

Страница 6: ...rick with a minimum of 3 thick 4 nominal Refractory mortar must be used at the junction of the chimney and the pass through liner The pass through liner must not penetrate the chimney liner beyond the...

Страница 7: ...nspector authorized J tul Dealer NFPA 211 in the U S or CAN CSA B635 in Canada for other approved wall pass through methods CONNECTING TO THE CHIMNEY Masonry Chimney When installing a OSLO F500 into a...

Страница 8: ...ust be installed to resize the flue A new sheet metal damper block off plate must be installed around the connector pipe at the damper frame and sealed with the proper sealant usually High Temp Silico...

Страница 9: ...can burn i e sheet rock wall paper wood fabrics etc These surfaces are not limited to those that are visible and also include materials that are behind non combustible materials If you are not sure o...

Страница 10: ...ceiling height off the top of the stove in a protected ceiling installation is 15 380mm 7 ALCOVE floor protection must be a UL ULC or WHI listed hearth pad or a non combustible materialwithaminimumRv...

Страница 11: ...PARALLEL TO THE WALL UNPROTECTED SURFACE CORNER INSTALLATION PROTECTED SURFACE PER NFPA 211 CORNER INSTALLATION IMPORTANT CONNECTOR HEATSHIELDS AND DOUBLE WALL PIPE MUST BE A LISTEDPRODUCT ALWAYS FOLL...

Страница 12: ...PROTECTED SURFACE NFPA 211 CLEARANCES pipe VERTICAL INSTALLATION VERTICAL INATALLATION Single wall 18 12 with no heatshields 460mm 300mm Single wall 6 6 with connector shields 150mm 150mm Double wall...

Страница 13: ...Breaking in your new stove Your new OSLO F500 is constructed of cast iron and stove furnace cement This type of construction requires the stove to be broken in gradually so that heat expansion does n...

Страница 14: ...FYOUNOTICETHISCONDITION Adding Fuel When reloading the stove while it is still hot and a bed of hot embers still exist follow this reloading procedure Always wear gloves when tending to the stove Push...

Страница 15: ...roper cleaning procedure is as follows 1 Glass needs to be COMPLETELY COOL 2 Only use a cleaner that is specifically designed for this purpose The use of abrasives will damage the glass and ultimately...

Страница 16: ...been approved for use as an open fireplace with front door open This feature is especially nice when the ambience of a fire is desired Some care should be taken when operating the stove as a fireplac...

Страница 17: ...Heatshield part 154332 A stove rear heatshield has been specifically designed for the OSLO F500 to reduce clearances off the rear of the stove to combustible materials Use of the heatshield DOES NOT a...

Страница 18: ...ED VIEW OF THE OSLO F500 ONLY USE REPLACEMENTS PARTS PROVIDED THROUGH YOUR AUTHORIZED J TUL DEALER 18 19 18 17 14 16 15 20 22 23 24 21 25 26 27 28 29 34 30 31 33 32 29 1 2 3 4 5 6 7 8 9 10 11 12 13 41...

Страница 19: ...f C 1 25 therefore R brick 1 C 1 1 25 0 80 1 8 mineral board of k 0 29 therefore R mineral board 1 29 X 0 125 0 431 Total R R brick R mineral board 0 8 0 431 1 231 Step C Compare proposed system R 1 2...

Страница 20: ...ue a policy of constant product development Products supplied may therefore differ in specification colour and type of accessories from those illustrated and described in the brochure J tul vise sans...

Отзывы: