30
3.0 Safety precautions
3.1 Fire preventive measures
Any use of the fireplace may represent some danger.
Therefore,
respect the following instructions:
• Ensure that furniture and other flammable materials do not
get too close to the fireplace.
• Let the fire die. Never put it out with water as this may
damage the product.
• The fireplace gets warm when used and may cause burns if
touched.
• Only remove the ashes when the fireplace is cold.
•
Ash must be properly disposed of outdoors, or emptied where
it does not entail a fire hazard.
3.2 Air supply
Warning!
Please ensure that there is adequate air supply from the
outdoors to the room in which the fireplace is to be installed.
An inadequate air supply could cause smoke gas to escape into
the room. This is very dangerous! Symptoms of this include smoky
smell, drowsiness, nausea and feeling ill.
Ensure that air vents in the room where the fireplace is located
are not blocked.
Avoid using mechanical fan vents in a room with a fireplace.
This may cause negative pressure and draw poisonous gasses
into the room.
4.0 Installation
4.1 Floor
Foundations
Ensure that the floor is strong enough for the fireplace. See
«2.0 Technical data»
for weights. Floor, which is not fixed to
the foundation (so-called floating floor) is reccomended to be
removed before installation.
Wooden floor protection
Jøtul I
80
has a heat shield beneath the bottom to protect the
floor from radiant heat.
Therefore the product can be mounted directly on a combustible
floor, if the floor is covered with a plate made of metal or or
other non-combustible material. The recommended minimum
thickness is 0,9 mm. The whole floor inside the surround must
be covered.
Any flooring made of combustible material, such as linoleum,
carpets, etc. must be removed from under the floor plate.
Requirement for protecting combustible
flooring in front of fireplace (fig. 1)
The front plate must be in accordance with national laws and
regulations
. Contact your local building authorities regarding
restrictions and installation requirements
.
4.2 Wall
Distance to combustible walls protected by
insulation material insulation/firewall - see fig. 1
Requirements for insulation
50 mm rock wool 120 kg/m
3
foliated on one side with
aluminium.
Distance from the insert heat shield to the
insulation on the wall
Minimum
15 mm
.
Distance from the insert heat shield to the firewall:
The distance must be
minimum 15 mm
.
Firewall requirement
The firewall must be at least
100 mm
thick and be made of
brick, concrete-stone or light concrete. Other materials and
constructions with satisfactory documentation may also be used.
Contact your local building authorities regarding restrictions and
installation requirements.
Requirements for the insert surround
The insert surround must be made in an incombustible material.
Note that the entire back panel within the surround must be
covered by insulation.
If the stove cowling is bricked up to the ceiling and the ceiling is
made of combustible material, on top of the warming chamber
and the cowling vents an extra ceiling panel must be installed
to avoid heating the ceiling.
ENGLISH
Содержание I 80 Maxi Classic
Страница 11: ...83...
Страница 13: ...85 A B B A A B B A Fig 11 g 10 E D C B A Fig 13 C E A B D ig 12 C B A B C D A Fig 15 ig 14...
Страница 14: ...86...
Страница 15: ...87...