Unitary Products Group
FIGURE 13 : FURNACE EVENT CONTROL SCHEDULE
TABLE 7: BLOWER PERFORMANCE CFM -UPFLOW/HORIZONTAL (WITHOUT FILTER)
Note: Data below reflects airflows with bottom return opening.
VOLTAGE
MOTOR
PULLEY
TURNS
EXTERNAL STATIC PRESSURE, INCHES W.C.
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
230 VAC
Closed
+
+
+
+
3467
3318
3163
2950
1 Open
3820
3687
3550
3406
3240
3066
2846
2589
2 Open
3575
3433
3269
3096
2913
2700
2449
2049
3 Open
3375
3205
2996
2807
2585
2293
1860
1026
4 Open
2805
2715
2570
2351
2017
1307
--
--
VOLTAGE
MOTOR
PULLEY
TURNS
EXTERNAL STATIC PRESSURE, INCHES W.C.
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
208 VAC
Closed
+
+
+
+
3383
3242
3100
2890
1 Open
3674
3555
3423
3283
3144
2990
2789
2555
2 Open
3543
3379
3213
3055
2888
2673
2420
1804
3 Open
3375
3210
3035
2850
2633
2334
1889
--
4 Open
3100
2919
2708
2498
2226
1724
--
--
+
Operation at these conditions will cause motor overload.
Operation in the shaded area may cause excessive furnace temperature rise.
NOTES: Airflow is expressed in standard cubic feet per minute.