background image

www.johnsonsystems.com

13

System Status - LED Indicators

RUN (Green)
Illuminates when the power is on, and the microcontroller status is in normal run mode. The LED 

flashes once every 2 seconds when the system is in STANDBY mode.
ØA, ØB and ØC (Green)
Illuminates when the line voltage power is within the acceptable range of 100-130 VAC for each 

phase, and the zero-cross reference circuitry is functioning properly. The LED will flash slowly 

(once per second) when an under-voltage state of less than 100 VAC is sensed, and will flash 

quickly (twice per second) when an over-voltage of greater than 130 VAC is sensed.
DMX A and DMX B (Yellow)
Illuminates when valid DMX is received on each of the inputs. Flashes when invalid DMX is 

received.
TERM A and TERM B (Yellow)
Illuminates when DMX is terminated on each of the inputs.
ALARM
Illuminates and flashes twice per second when either a fire or security alarm is sensed on each of 

the inputs. 
O/T
Illuminates and flashes twice per second whenever one of three over-temperature sensing inputs 

are triggered.

System Status - LCD Display

When DMX is being received, the top line of the LCD display shows the active DMX MODE (“PTY 

A”, “PTY B”, “MERGE”, “DMX A+B”, “2 ROOM” or “PATCH”).  When DMX is not being received, 

the top line of the LCD display shows “MADD-24”, unless the system is in standby mode, then 

“STANDBY!” is displayed.
The bottom line of the LCD Display shows the current status of the system, unless the system 

configuration menu items are being accessed. Below are descriptions for each status indication.
NO RX!
Displayed when DMX is not being received on either input, and the system is not in scene mode.
AXXXBXXX
Displayed when valid DMX is being received on one or both inputs, and both inputs are not 

terminated. “A” and “B” represent the DMX A and DMX B inputs, while “XXX” represents the 

number of channels being received in each packet of data. For example, if the system is receiving 

512 channels on DMX B and DMX A is disconnected, the display will show “A000B512”. 

   

XXX

    

XXX

Same as above, except the “A” and “B” is replaced with “  ” to indicate if one or both of the DMX 

inputs are terminated. For example, if the system is receiving 48 channels on DMX A and 512 

channels on DMX B, with only DMX A terminated, the display will show “

    

048B512”. Refer to 

menu items “DMXA TRM” and “DMXB TERM” on page 18 and 19 for further details.
SH XX:YY
Displayed when DMX is disconnected, and the systems predetermined DMX status hold (SH) 

time is counting down. “XX” represents minutes, while “YY” represents seconds. Refer to menu 

item “SH TIME” on page 21 for further details.

Содержание JS-ICON 1210

Страница 1: ...User Manual JS ICON Series Dimmer Rack JS ICON 2410 JS ICON 2413 JS ICON 1220 JS ICON 1210 620 JOHNSON SYSTEMS INC www johnsonsystems com ...

Страница 2: ... neither of the above can provide you with the necessary information please contact our factory via email info johnsonsystems com or phone 403 287 8003 during business hours Monday to Friday 8 00AM to 5 00PM MST Contents Warranty 2 For Technical Assistance 2 Introduction 3 Characteristics 4 Installation 5 Power Supply Connection Details 6 Ground Connection Details 8 Dimmer Output 9 Control Input O...

Страница 3: ... thermal management technology produces superior cooling that is virtually silent making JS ICON the natural choice for quiet space dimming installations Exclusive lamp warming techniques extends lamp life considerably while maintaining industry leading performance Available in multiple sizes and configurations Unique power saving stand by mode reduces power consumption to less than 1 Watt Complia...

Страница 4: ...Incandescent quartz lamps and electronic SCR dimmable low voltage fixtures Relay Load Type Any to maximum circuit rating Switch Type 200 rated non proprietary SCR solid state relay Choke Type High performance copper wound hybrid core toroidal magnetic filter Choke Rise Time 2400W 400µs 1560W 300µs 1200W 300µs Physical 30 x 17 x 6 8 75 cm x 43 cm x 17 cm Weight All Models approximately 66 lbs 30 Kg...

Страница 5: ...O OFF I ON O OFF O OFF I ON O OFF I ON I ON O OFF I ON 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 2002161 I ON O OFF O OFF O OFF I ON O OFF I ON O OFF I ON O OFF I ON I ON O OFF I ON O OFF I ON O OFF I ON O OFF I ON O OFF I ON O OFF I ON O OFF I ON O OFF O OFF I ON I ON O OFF O OFF I ON O OFF I ON I ON O OFF I ON O OFF I ON O OFF O OFF I ON O OFF I ON I ON O OFF I ON 1 2 3 4 5 ...

Страница 6: ...l only WARNING Be sure all power connections are tightened to specification before power supply is turned on Power Supply Configurations Three Phase 120 208 VAC 3Ø 5 Wire up to 100 Amps per phase Maximum 28 8kW total Use wire size 14 to 1 0 AWG Strip insulation length to 0 65 16 5mm Torque power terminals A B C to 45 50 IN LBS 5 0 5 6 NM Below is the dimmer phasing for each JS ICON Series dimmer r...

Страница 7: ...ase contact your supplier for a single phase conversion kit if required The following steps will need to be followed to convert the JS ICON dimmer rack from three phase to single phase operation 1 Remove the three phase copper bussbars by loosening all of the screws terminals use a medium sized 2 Philips or Flathead screwdriver on the left hand side of the circuit breakers 2 Insert the supplied si...

Страница 8: ... 2 3 2 8 NM Models JS ICON 2410 JS ICON 2413 and JS ICON 1210 620 are supplied with 25 load circuit neutral terminals while Model JS ICON 1220 is supplied with 12 NOTE For connection use copper wire only rated for 167 F 75 C minimum Ground Connection Details Ground Input Terminal Use wire size 14 to 1 0 AWG Strip insulation length to 0 65 16 5mm Torque ground terminal to 45 50 IN LBS 5 0 5 6 NM Th...

Страница 9: ...onic low voltage fixtures The dimmer outputs may be configured for non dimmed applications when switched relay controlled load outputs are required Knockouts on the top and bottom of the chassis are provided for wire conduit entry to the power terminals Load Hot Output Connection Details Load output connections are terminated via DIN rail mounted terminal blocks Models JS ICON 2410 and JS ICON 241...

Страница 10: ...omplies with USITT DMX512 A ANSI E1 11 2008 Standard protocol for digital data control Recommended cable is Belden 9829 9842 Cat 5 or equivalent low capacitance twisted pair Wiring must follow a daisy chain topology Maximum of 32 receiving devices on a single DMX line Maximum cable length is 1 500 feet 455 meters For more information Google DMX or visit http old usitt org DMX512FAQ aspx NOTE Ensur...

Страница 11: ... to low voltage common COM Fire Alarm Input Normally Open Terminate FIRE on J11 connector Triggers selected channels to turn on when contact switch is closed Controlled via a maintained contact switch to low voltage common COM Programmed in the F ALARM menu See page 25 for details Security Alarm Input Normally Open Terminate SCTY on J11 connector Triggers selected channels to cycle on and off at a...

Страница 12: ...em LCD VIEW on page 30 for further details Programming Switches The MENU UP DOWN switches are used for navigating through the various system configuration menu items They also allow for programming of other specific parameters within a selected menu Pressing and holding either switch will speed up the scroll rate which can be helpful to speed up the configuration time The EXECUTE switch is normall...

Страница 13: ...MX A B 2 ROOM or PATCH When DMX is not being received the top line of the LCD display shows MADD 24 unless the system is in standby mode then STANDBY is displayed The bottom line of the LCD Display shows the current status of the system unless the system configuration menu items are being accessed Below are descriptions for each status indication NO RX Displayed when DMX is not being received on e...

Страница 14: ...dimmer outputs are disabled and the fans are turned on to full until the temperature cools down to 178 F 81 C or less Refer to menu item REM TEMP on page 26 to view the current remote temperature CTL TEMP Displayed when the microcontroller senses an internal over temperature condition of 185 F 85 C or more All dimmer outputs are disabled and the fans are turned on to full until the temperature coo...

Страница 15: ...puts when DMX is being received 24 STANDBY Enable or disable the power savings standby mode 25 TEST INC Set the test increment units to percent or hexadecimal 26 OC MODE Configure the input trigger parameters for the open collector output 27 AUX IN Select which scene the auxiliary input will trigger enable 28 L BUTTON Set the mode of the local buttons to scene bump or disabled 29 S ALARM Select th...

Страница 16: ...D indicates the control channel C and level L C 24L 00 Press MENU to select the control channel C to modify from 01 to 24 C 24L 00 Press EXECUTE to toggle from channel C to level L selection C 24L 00 Press ESCAPE to toggle from level L to channel C selection C24L FL Press MENU to select the output level L for the selected channel from 00 to FL CLEAR Press EXECUTE to clear the selected preset and s...

Страница 17: ...This menu does not timeout automatically and will continue to monitor indefinitely Press EXECUTE to enter the menu and activate monitor mode D 01L000 Press MENU to select the dimmer D output to monitor from 01 to 96 D 24L512 Display shows dimmer 24 has full on control Press ESCAPE or RESET to exit the menu NOTE The control value will not reach 512 when voltage output limiting is activated or when ...

Страница 18: ...saved NOTE DMX O P must be set to OFFSET mode for this menu to function 8 2 RM SET Set the two room assignment for each of the dimmer outputs This menu is used to assign each of the 24 dimmer outputs to room A or room B Dimmer outputs assigned to room A are controlled via the DMX A input Dimmer outputs assigned to room B are controlled via the DMX B input This creates separation within the dimmer ...

Страница 19: ...enable ENABLED Press and hold MENU and MENU at the same time for 4 5 seconds OFFSET Press EXECUTE to toggle the DMX mode from OFFSET to PATCH PATCH Press EXECUTE to toggle the DMX mode from PATCH to OFFSET Press ESCAPE or RESET to exit the menu Any change in the configuration is automatically saved 12 DMXA PAT Patch the 24 dimmer PWM outputs to any DMX A input channel There are two ways to configu...

Страница 20: ...ck DIM 024 Press MENU to edit the dimmer number DIM from 001 to 024 DIM 001 Press MENU and MENU at the same time to toggle back to 001 DMXA 001 Press EXECUTE to select the DMX A DMXA start address for the block DMXA 512 Press MENU to edit the DMX A DMXA start address from 001 to 512 DMXA 001 Press MENU and MENU at the same time to toggle back to 001 DIM 001 Press EXECUTE to select the number of di...

Страница 21: ...CUTE to toggle the pointer to select the control channel to patch D24 C01 Press MENU to select the desired control channel from 01 to 24 D24 C01 Press EXECUTE to toggle the pointer to select another dimmer output Press ESCAPE to exit the menu and save the desired dimmer channel patch Press RESET to exit the menu without saving The menu will automatically timeout after 2 minutes of inactivity and s...

Страница 22: ... level for the selected dimmer outputs Load shed SHED mode is used as a power management interface to building management systems BMS Contact closure devices such as a photocell or maintained switch contact may be used to trigger the analog input When a voltage of 5 5VDC to 12VDC is sensed on the analog input the selected dimmer outputs are disabled set to zero output level The selected dimmer out...

Страница 23: ...nputs and functions in a highest takes precedence HTP mode of operation ENABLED Press EXECUTE to toggle analog blocking from ENABLED to DISABLED DISABLED Press EXECUTE to toggle analog blocking from DISABLED to ENABLED Any change in the configuration is automatically saved 24 STANDBY Enable or disable the power savings standby mode When standby mode is enabled the microcontroller goes to sleep wit...

Страница 24: ...ith JS ICON Series dimmer racks Setting the local buttons to scene mode puts the system in scene mode With scene mode enabled the selected scene will always be activated when DMX is not being received The selected scene can be changed in the SCENESET menu Scene mode enables the use of the auxiliary AUX input A contact closure sensed on the over temperature O T fire alarm FIRE or security alarm SCT...

Страница 25: ...chase effects the delay may be undesirable in which case the lamp warming feature can be turned off Note that when standby mode is enabled the microcontroller goes to sleep within 5 seconds of inactivity on the control inputs and there is delay of 150 milliseconds for the microcontroller to wake up and restart normal run mode To ensure virtually instant dimmer control response set STANDBY to DISAB...

Страница 26: ...e menu and view the line voltage of each phase ØA 120 0 Shows the line voltage of Phase A ØB 120 0 Press MENU to view the line voltage of Phase B ØC 120 0 Press MENU to view the line voltage of Phase C Press ESCAPE or RESET to exit the menu 35 LINE F View the line frequency of phase A 60 0 Hz Shows the frequency 36 REM TEMP View the temperature of the remote temperature sensor A thermostat measure...

Страница 27: ...desired hard key code Press RESET to exit the menu without saving The menu will automatically timeout after 2 minutes of inactivity and save NOTE Be sure to record and file the hard key code on page 31 for future reference 40 SERIAL View the microcontroller s unique six character silicone serial number XXXXXX Shows the unique six character serial number 41 VERSION View the microcontroller s softwa...

Страница 28: ...ed if the wrong product type of EEPROM memory module detected PRODUCT Displayed if the wrong product type of EEPROM memory module detected CRC ERR Displayed if the CRC test fails and the EEPROM memory module is defective WARNING Do not reset or turn the power off while the firmware is being updated Doing so will cause unrecoverable loss of firmware data that is being loaded into the MADD 24 microc...

Страница 29: ...RIFY Automatically verifies parameter backup data and CRC value DONE Parameter backup is done and saved in the EEPROM memory module NO MEM Displayed if an EEPROM memory module is not detected WRONG Displayed if the wrong type parameter of EEPROM memory module detected MEM TYPE Displayed if the wrong type parameter of EEPROM memory module detected WRONG Displayed if the wrong product type of EEPROM...

Страница 30: ... is AAAAAAAAAAAABBBBBBBBBBBB ØPATCH5 Phase patch for JS ICON 1220 with Single Phase power Dimmer phase assignment is AAAAAABBBBBB 13 24 are unused ØPATCH6 Phase patch for JS ICON 1210 620 with Single Phase power Dimmer phase assignment is AAAAAAAAAAAABBBBBB 19 24 are unused ØPATCH7 Patches all PWM output channels to ØA Not used with JS ICON product ØPATCH8 Phase patch for DE90 3000 Series retrofit...

Страница 31: ...Serial Number ________________ Hard Key Code ______________________ JSI Serial Number ____________________ Silicone Serial Number ________________ Hard Key Code ______________________ JSI Serial Number ____________________ Silicone Serial Number ________________ Hard Key Code ______________________ JSI Serial Number ____________________ Silicone Serial Number ________________ Hard Key Code _______...

Страница 32: ...ms com 32 Troubleshooting Reference This manual is accurate at time of printing and subject to revisions and technical updates as required without prior notice Please visit www johnsonsystems com for applicable updates ...

Страница 33: ...ms com 33 Troubleshooting Reference This manual is accurate at time of printing and subject to revisions and technical updates as required without prior notice Please visit www johnsonsystems com for applicable updates ...

Страница 34: ... 2400 Watt dimmers JS ICON 2410 24 x 10 Amp 1200 Watt dimmers JS ICON 2413 24 x 13 Amp 1560 Watt dimmers JS ICON 1210 620 12 x 10 Amp 1200 Watt 6 x 20 Amp 2400 Watt dimmers JSI ICON Series Dimmer Relay Racks User Manual JS ICON Series Dimmers Rev 3 ...

Отзывы: