Table 58: Fault Codes
SR. No.
Condition
Red LED
Green LED
21
Fan only (No
heat/cool)
Off
Fast heartbeat
22
No alarms
in memory
2 pulses
2 pulses
23
Normal idle
Off
Slow heartbeat
24
Factory test mode
Rapid flash
Rapid flash
Push Button
Hold down for:
•
0 to 2 seconds: 5 most recent error codes in
the history will flash on the LEDs
•
2 to 5 seconds: clear anti-short cycle timers
and reset any active lockouts
•
> 5 seconds: clear all fault history