18
Zone Terminal
Use a flat-head screwdriver and insert it in the bottom where the ZT and
mounting base come together. Gently pry the ZT out of the mounting
base. As you push the screwdriver in, the ZT slides up and then out.
REMOVAL
Figure 13: Removing Mounted ZT
The ZT can be connected directly to the:
●
Air Handling Unit (AHU)
●
Function Module Kit (FMK)
●
Relay Kit (RLY)
●
Actuator (M100C)
●
Zone Sensor (TE-6100)
Figure 14 shows you where to locate the telephone-style plugs in each of
these components.
Notes:
If ZT is connected 50 feet or less from the controller, install 24
AWG telephone cable between the controller and the ZT.
If ZT is connected up to 500 feet from the controller, install 18
AWG wire. The ZT requires 24 VAC, Common, and Zone Bus.
Removing a
Mounted ZT
Connecting the ZT