14
Zone Terminal
Prior to connection, the ZT must be downloaded using the
ZT PRO
software tool which is part of the
HVAC PRO Rev. 3.0.
Refer to the
HVAC PRO User’s Manual, ZT PRO
Section.
If ZT is connected 50 feet or less from the controller, install 24 AWG
telephone cable between the controller and the ZT.
If ZT is connected up to 500 feet from the controller, install 18 AWG wire.
The ZT requires 24 VAC, Common, and Zone Bus.
Before you mount the ZT or connect it to a controller, the clear plastic
insert that describes the displayed values must be in place.
1. Lay the ZT flat and press the white tab on the top of the ZT while
pulling the front cover towards you.
2. Align the insert to the lower left front of the ZT.
3. Press the pieces back together.
INSERT2
Figure 7: Template Installation
Connecting the
Zone Terminal
Wiring
Considerations
Installing the
Inserts