ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions

2

Installation

Follow these guidelines when installing a 
ZFR1812 Router:

Transport the ZFR1812 Router in the original 
container to minimize vibration and shock damage.

Do not drop the ZFR1812 Router or subject it to 
physical shock.

Materials and Special Tools Needed

A 1.5 mm (1/16 in.) Allen wrench or a Johnson 
Controls® T-4000-119 Allen-Head Adjustment Tool 
is required for tightening or loosening the security 
screw

Dimensions

See Figure 1 for physical features and dimensions of 
the ZFR1812 Router.  

Mounting

Note:

These instructions are for mounting new 

ZFR1812s rather than retrofitting factory-mounted 
routers.

The ZFR1812 can be mounted directly to drywall with 
drywall anchors. Both the standalone and repeater kit 
versions of the ZFR1812 include a 10 foot long RJ12 
cable hardwired to the device. The Repeater Kit 
versions (the ZFRRPTK-H1 and ZFRRPTK-H2) 
provide additional flexibility for mounting such as a 
separate power supply. ZFR1812s can be flush 
mounted to a wall or ceiling, or mounted on a 4x4 box 
using a standard mudplate. When mounting the 
ZFR1812 Router to an enclosure, mount it to the top, 
bottom, or side of the enclosure. For floor mount 
unitary equipment, mounting on top where books or 
other items may be placed is not ideal. Se

Location 

Considerations

.

Mounting Directly to Drywall with Drywall Anchors 
- ZFR1812

1.

Separate the plastic base and circuit board 
assembly (cover). Do not remove the security 
screw from the cover. See Figure 2.

IMPORTANT:

The label showing the unit MAC 

address is on the plastic base of the unit. Be sure to 
keep the plastic base and circuit board assemblies 
together so the correct MAC address is shown.

2.

Determine where to secure the plastic base to the 
surface using the mounting holes and supplied 
screws. A template (Figure 11) is provided at the 
end of this document to help you place the 
mounting holes.

3.

Set the DIP switches. (See 

Setup and Adjustments 

).

4.

Reattach the circuit board assembly in the plastic 
base being careful not to pinch the attached RJ-12 
cable.

5.

Tighten the security screw to prevent tampering 
using a 1.5 mm (1/16 in.) Allen wrench or a 
Johnson Controls® T-4000-119 Allen-Head 
Adjustment Tool. Use caution when tightening the 
screw to avoid stripping the plastic threads in the 
ZFR1812.

Mounting the ZFRRPTK-H1

The ZFRRPTK-H1 is intended for flush wall mount or 
ceiling mount applications. In addition to the ZFR1812, 
it includes a power supply, a 10 ft RJ-12 cable for 
connecting the power supply, and an adapter to 
connect the power supply to the RJ-12 cable.

To mount the ZFRRPTK-H1:

1.

Separate the plastic base and circuit board 
assembly (cover). Do not remove the security 
screw from the cover. See Figure 2.

Figure 1: ZFR1812 Wireless Field Bus Router, 

Physical Features and Dimensions, mm (in.)

Содержание ZFR1812

Страница 1: ...es Wireless Field Bus System Quick Reference Guide LIT 12011630 for information on commissioning and configuring a ZFR1800 Series Wireless Field Bus System for operation North American Emissions Compliance United States Canada Use the ZFR1812 Wireless Field Bus Router only to provide an input to equipment under normal operating conditions Where failure or malfunction of the ZFR1812 Router could le...

Страница 2: ...deal See Location Considerations Mounting Directly to Drywall with Drywall Anchors ZFR1812 1 Separate the plastic base and circuit board assembly cover Do not remove the security screw from the cover See Figure 2 IMPORTANT The label showing the unit MAC address is on the plastic base of the unit Be sure to keep the plastic base and circuit board assemblies together so the correct MAC address is sh...

Страница 3: ...g the ZFR1812 flush for a professional appearance A hole is provided in the base of the assembly for this purpose Figure 3 IMPORTANT If you are using a ceiling mounting clip you must make sure that no part of the clip makes contact with the circuit board assembly when installed 3 Assemble the external power and adapters as necessary Figure 4 a The 24 VAC to 15 VDC power supply 1 uses screw termina...

Страница 4: ... the circuit board assembly in the plastic base 6 Tighten the security screw to prevent tampering using a 1 5 mm 1 16 in Allen wrench or a Johnson Controls T 4000 119 Allen Head Adjustment Tool Use caution when tightening the screw to avoid stripping the plastic threads in the ZFR1812 7 Assemble the external power and adapters as necessary Figure 4 Note that the power supply can be secured in an e...

Страница 5: ...810 Coordinator ZFR1812 Router and a WRZ Sensor can be less than the maximum distances shown in Table 1 The effective transmission range for indoor applications varies because of wireless signal absorption and reflection due to metal obstructions walls or floors and furniture found in typical building interiors Wiring Wiring Considerations and Guidelines Wiring with an FEC or VMA16 Series Field Co...

Страница 6: ...AC26 FC Bus RJ 12 Jack SA Bus RJ 12 Jack SA Bus Terminals FAC36 FC Bus RJ 12 Jack SA Bus RJ 12 Jack SA Bus Terminals FEC16 FC Bus RJ 12 Jack SA Bus RJ 12 Jack SA Bus Terminals FEC26 FC Bus RJ 12 Jack SA Bus RJ 12 Jack SA Bus Terminals IOM172 3 SA FC Bus RJ 12 Jack Not available in wireless mode Use CCT with ZFR Dongle N A IOM272 3 SA FC Bus RJ 12 Jack Not available in wireless mode Use CCT with ZF...

Страница 7: ... then all on and then set the switches to the desired PAN Restore power to the ZFR1812 and see that it joins the correct network If the ZFR1812 misread the dip switches it might become the child of another network and use up an available child slot in a device you did not expect If this situation occurred a reform on the incorrect network should clear up the now unusable child address Note On some...

Страница 8: ...Wireless Room Temperature Sensors Installation Instructions Part No 24 10332 2 for more information Approximately once every 10 seconds the Signal Strength LED flashes to indicate the strength of the signal received from neighboring devices See Table 3 Note The Signal Strength LEDs on all the ZFR1812 routers in a network extinguish after approximately 2 hours of normal operation making the ZFR1812...

Страница 9: ...trength 3 Flashes Excellent 2 Flashes Good 1 Flash Weak OFF for 3 seconds None Network Reform Operation during network reform Rapid Flashes for 5 minutes rapid flashes occur for up to 5 minutes when the Reform Network option is initiated to the network the ZFR1812 Router disconnects itself from the network when the PAN OFFSET is changed on the ZFR1812 Router when the PAN OFFSET is changed on the Z...

Страница 10: ...FR router is better facilitated using a Inch conduit EMT connector MS ZFRRPTK H1 ZFR1812 0 wireless router repeater kit Includes ZFR1812 router 24 VAC to 15 VDC power supply RJ 12 cable for power extension and mounting hardware Use the ZFRRPT H1 for flush wall mount or ceiling mount applications MS ZFRRPTK H2 ZFR1812 0 wireless router repeater kit Includes ZFR1812 router 24 VAC to 15 VDC power sup...

Страница 11: ... for the repeater power supply has a flexible input power range and provides regulated 12 VDC output Input power 20 28 VAC at 78 62 mA maximum 16 30 VDC at 45 28 mA maximum Output power 12 VDC regulated at 500 mA maximum Current Consumption 90 mA maximum Addressing DIP Switches Field Adjustable Wireless Band Direct Sequence Spread Spectrum 2 4 GHz ISM Bands Transmission Power 10 mW Maximum Transmi...

Страница 12: ...810 1 279A WRZRADIO Australia and New Zealand RCM Mark Australia NZ Emissions Compliant Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provisions of the RED Directive The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications cons...

Страница 13: ...tion Instructions Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2016 Johnson Controls Inc Building Efficiency 507 E Michigan Street Milwaukee WI 53202 13 Figure 11 ZFR1812 Mounting Template Scale 1 000 ...

Отзывы: