ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
2
Installation
Follow these guidelines when installing a
ZFR1812 Router:
•
Transport the ZFR1812 Router in the original
container to minimize vibration and shock damage.
•
Do not drop the ZFR1812 Router or subject it to
physical shock.
Materials and Special Tools Needed
•
A 1.5 mm (1/16 in.) Allen wrench or a Johnson
Controls® T-4000-119 Allen-Head Adjustment Tool
is required for tightening or loosening the security
screw
Dimensions
See Figure 1 for physical features and dimensions of
the ZFR1812 Router.
Mounting
Note:
These instructions are for mounting new
ZFR1812s rather than retrofitting factory-mounted
routers.
The ZFR1812 can be mounted directly to drywall with
drywall anchors. Both the standalone and repeater kit
versions of the ZFR1812 include a 10 foot long RJ12
cable hardwired to the device. The Repeater Kit
versions (the ZFRRPTK-H1 and ZFRRPTK-H2)
provide additional flexibility for mounting such as a
separate power supply. ZFR1812s can be flush
mounted to a wall or ceiling, or mounted on a 4x4 box
using a standard mudplate. When mounting the
ZFR1812 Router to an enclosure, mount it to the top,
bottom, or side of the enclosure. For floor mount
unitary equipment, mounting on top where books or
other items may be placed is not ideal. See
.
Mounting Directly to Drywall with Drywall Anchors
- ZFR1812
1.
Separate the plastic base and circuit board
assembly (cover). Do not remove the security
screw from the cover. See Figure 2.
IMPORTANT:
The label showing the unit MAC
address is on the plastic base of the unit. Be sure to
keep the plastic base and circuit board assemblies
together so the correct MAC address is shown.
2.
Determine where to secure the plastic base to the
surface using the mounting holes and supplied
screws. A template (Figure 11) is provided at the
end of this document to help you place the
mounting holes.
3.
Set the DIP switches. (See
).
4.
Reattach the circuit board assembly in the plastic
base being careful not to pinch the attached RJ-12
cable.
5.
Tighten the security screw to prevent tampering
using a 1.5 mm (1/16 in.) Allen wrench or a
Johnson Controls® T-4000-119 Allen-Head
Adjustment Tool. Use caution when tightening the
screw to avoid stripping the plastic threads in the
ZFR1812.
Mounting the ZFRRPTK-H1
The ZFRRPTK-H1 is intended for flush wall mount or
ceiling mount applications. In addition to the ZFR1812,
it includes a power supply, a 10 ft RJ-12 cable for
connecting the power supply, and an adapter to
connect the power supply to the RJ-12 cable.
To mount the ZFRRPTK-H1:
1.
Separate the plastic base and circuit board
assembly (cover). Do not remove the security
screw from the cover. See Figure 2.
Figure 1: ZFR1812 Wireless Field Bus Router,
Physical Features and Dimensions, mm (in.)