Reassembly
This section provides technical specifics for the chiller, including weights, dimensions, and torque
requirements.
Note:
The YVAM chiller is completely factory assembled and does not require any field
assembly. For occasions where field disassembly or reassembly may need to be conducted
for any reason, the following sections are intended to provide technical details for a qualified
Johnson Controls Service representative to safely complete these tasks.
Table 8: Assembly torque metric for metric tube fittings
Torque
Fitting size
Port thread size
ft·lb
N•m
M10
M10 x 1
17
23
M12
M12 x1.5
24
33
M14
M14 x 1.5
34
46
M16
M16 x 1.5
46
63
M18
M18 x 1.5
61
83
M22
M22 x 1.5
94
127
M27
M27 x 2
139
189
M30
M30 x 2
167
226
M33
M33 x 2
194
263
M42
M42 x 2
265
359
M48
M48 x 2
302
410
M60
M60 x 2
359
487
Table 9: Assembly torque values for SAE tube fittings
Tube size
SAE straight thread size
(O-ring part number)
SAE straight thread
torque, ft·lb
Face seal tube-side
thread size (O-ring part
number)
Face seal tube-side
torque, ft·lb
1/4 in.
7/16-20
(028-12961-001)
25
9/16-18
(028-12961-011)
18
3/8 in.
9/16-18
(028-12961-003)
35
11/16-16
(028-12961-012)
30
1/2 in.
3/4-16
(028-12961-004)
60
13/16-16
(028-12961-013)
40
5/8 in.
7/8-14
(028-12961-005)
100
1-14
(028-12961-014)
60
3/4 in.
1 1/16-12
(028-12961-006)
135
1-3/16-12
(028-12961-015)
85
1 in.
1 5/16-12
(028-12961-008)
200
1-7/16-12
(028-12961-016)
110
1 1/4 in.
1 5/8-12
(028-12961-017)
250
1-11/16-12
(028-12961-022)
140
1 1/2 in.
1 7/8-12
(028-12961-020)
305
2-12-UN2A
(028-12961-019)
180
= SAE
sightglass
2 1/4-12
(028-12961-)
225
—
—
29
YVAM Air-Cooled Centrifugal Liquid Chiller