6. To complete the installation, reinstall the top bolt and washer and tighten.
Figure 16: Elastomeric isolator details
Callout
Description
Callout
Description
A
Isolator base
B
Base slotted holes
C
Isolator threaded hole
D
Cross section points
E
Top washer
F
Top bolt
Note:
Isolators generally appear square or rectangular in appearance.
Figure 17: Elastomeric isolator cross reference, Type A isolators
Table 6: Elastomeric isolator dimension data, in. (mm)
Model P/N
L
W
HF
AL
AD
BT
CD
DW
Type A 029-25335-001
(434002)
5.50
(139.70)
3.38
(85.85)
2.88
(73.15)
4.13
(104.90)
0.56
(14.22)
0.25
(6.35)
1/2-13 UNC x 1
(M27 x 3)
2.50
(63.50)
Type B 029-25335-002
(434004)
Type B 029-25335-004
(434005)
6.25
(158.75)
4.63
(117.6)
2.75
(69.85)
5.00
(127.00)
0.56
(14.22)
0.38
(9.65)
1/2-13 UNC x 1
(M27 x 3)
3.00
(76.20)
23