System screen
Figure 13: System screen
This screen gives a general overview of common chiller parameters for both shells.
Table 13: Display only fields
Field/LED name
Description
Discharge Temperature
Displays the temperature of the refrigerant in its gaseous state at discharge of the
compressor as it travels to the condenser.
Input % Full Load Amps
This displays the percentage of full load amps utilized by the system.
Outside Ambient Temperature
Displays the outside ambient air temperature.
Chilled Liquid Temperature - Leaving Displays the temperature of the liquid as it leaves the evaporator.
Chilled Liquid Temperature -
Entering
Displays the temperature of the liquid as it enters the evaporator.
Chilled Liquid Temperature -
Setpoint
Displays the programmed temperature setpoint for leaving chilled liquid. It is the local
value or remote reset value depending on control source.
Condenser Pressure
Displays the refrigerant pressure in the condenser.
Condenser Saturation Temperature Displays the saturation temperature in the condenser calculated from condenser
pressure.
Evaporator Pressure
Displays the present refrigerant pressure in the evaporator.
Evaporator Saturation Temperature Displays the present saturation temperature in the evaporator calculated from
evaporator pressure.
Programmable
There are no programmable fields on this screen.
Table 14: Navigation
Button
Description
Home
Causes an instant return to the Home screen.
YVAM Control Center
36
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...