Domestic Air Conditioner
Functions and Control
When compressor stands by for 3 minute and the temp. of coil pipe is below 50 , the unit can be started
again.
*Current protection and current expiration protection: (Not detecting within 60 seconds after start up)
*Overcooling protection One and half a minutes later after compressor starts, if the temperature of
coil pipe is below -4 , compressor and air outlet stop, and air inlet runs according to the temp. setting.
Compressor can be restarted 3 minutes later.
5.1.5.3 Defrosting:
5.1.5.3.1 Entry conditions of defrosting:
The entry conditions of defrosting is classified into two types: intelligentized defrosting and sensor
defrosting. Through selecting and judging, the models without outdoor sensor defrosts according to
intelligentized defrosting, and others with ensor defrosts according to sensor defrosting.
Intelligentized defrosting:
5.1.5.3.1.1 Indoor unit enter overload protection and air outlet stops when air outlet has been
restarted and runs over 10 minutes, and compressor runs over 45 minutes in total and over 20 minutes
continuously, and the temp. of indoor coil pipe is below 38 .
5.1.5.3.1.2 Compressor runs20minutes continuously, and the temp. of indoor coil pipe decreases
1
per 6 minutes and this operation repeats 3 times, and the temp. of coil pipe is below 38 , and 5
minutes later after compressor is restarted.
5.1.5.3.1.3 When compressor runs over 3 hours in total and over 20 minutes continuously and after
the temp. of indoor coil pipe is below 38 , the system enters defrosting mode.
5.1.5.3.1.4 The difference between the temp. of indoor coil pipe and the indoot temp. is below 16
and lasts 5 minutes, compressor runs over 45 minutes in total and over 20 minutes continuously after the
temp. of indoor coil pipe is below 38 , the system enters defrosting mode.
5.1.5.3.2 Exit conditions of defrosting:
Defrosting time is higher than 12 minutes (compressor is on).
5.1.5.3.2.1 During the defrosting, if current peak value is cut off, the unit quit the defrosting mode.
But the protection of expiration of current peak value is unavailable with 60 senconds after compressor is
started.
5.1.5.3.2.2 During the defrosting and 2 minutes After quiting the defrosting mode, abnormality of
temp. sensor isn’t detected.
5.1.5.3.2.3 After quiting the defrosting mode, the fan motor enter cooling prevention mode.
YSCC/H07/09/12FSAADG
15
Содержание YORK YSCC/H09FSAADG
Страница 37: ...YSCC H07 09 12FSAADG 35 ...
Страница 50: ...8 5 Sound level YSCC H07FSAADG YSCC H07FSAADG pressure M L 36 33 28 48 220V 60HZ YSCC H07 09 12FSAADG 48 ...
Страница 51: ...YSCC H09FSAADG pressure M L 39 34 30 YSCC H09FSAADG 50 220V 60HZ 49 YSCC H07 09 12FSAADG ...
Страница 52: ...YSCC H12FSAADG pressure M L 39 35 31 YSCC H12FSAADG 39 220V 60HZ YSCC H07 09 12FSAADG 50 ...
Страница 57: ...Domestic air conditioner Piping diagrams YSCC H07 09 12FSAADG 55 ...
Страница 61: ...Dimensional drawings 10 4 Dimensional drawings YSCC H07 09FSAADG YSCC H12FSAADG YSCC H07 09 12FSAADG 59 ...
Страница 67: ...The end YSCC H07 09 12FSAADG ...